7. Switching modules
49
Operation
The bus signal of the controller activates one or several outputs of the switching module. Alternatively, the outputs can be
activated or deactivated manually using the buttons on the switching module. Please remember that the activation or
deactivation is only temporary as it will be overruled by the next bus communication.
The outputs are activated or deactivated via low-energy bistable relays in the switching module. The status of the relay
only changes when a data pulse is generated by the controller or by one of the switch buttons.
Permitted loads
Check the table below to find out the maximum load for each type of lighting.
Type of lighting
Maximum RMS current
energy-saving lamps (CFLi), LEDs and HF fluo lamps with electronic control gear – ECG
3 A
fluorescent lamps
(parallel compensated)
6 A
fluorescent lamps
(non-compensated or serial-compensated)
10 A
low-voltage halogen lamps with ferromagnetic or electronic transformers
10 A
incandescent lamps, 230V halogen lamps
(resistive loads)
16 A