70
9. Electricity measuring modules
Technical data
Electricity measuring module with one channel
• input voltage: 230 Vac
• measurement range: 5 - 14 500 W, 22 mA - 63 A
• accuracy: IEC62053-21 class 1 (R), class 2 (L)
• single-phase connection: 230 Vac, 50 Hz
• 1 current clamp (included)
• max. cable thickness for the current clamp: 1 x 10 mm² or 6 x 2,5 mm² or 9 x 1,5 mm²
• length of the connector cable at the current clamp: 100 cm
• 4 connection terminals to measure the voltage of the connected circuit
• 2 connection terminals to connect the current clamp supplied
• sliding contact
• dimensions: DIN 2U
• CE marking
• ambient temperature: 0 - 45°C
Electricity measuring module with three channels
• input voltage: 230 Vac
• measurement range: 5 - 14 500 W, 22 mA - 63 A
• accuracy: IEC62053-21 class 1 (R), class 2 (L)
• connection:
• three-phase: 3N 400 Vac, 50 Hz
• single-phase: three switching circuits of 230 Vac, 50 Hz
• 3 current clamps (included)
• max. cable thickness for the current clamp: 1 x 10 mm² or 6 x 2,5 mm² or 9 x 1,5 mm²
• length of the connector cable at each current clamp: 100 cm
• 4 connection terminals to measure the voltage of the connected circuit
• 2 connection terminals to connect the current clamp supplied
• sliding contact
• dimensions: DIN 4U
• CE marking
• ambient temperature: 0 - 45°C