88
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
07.16
: Analog input 3 scaling
Adjustment range : Input: 0.00 to 2.50
Factory setting : 1.00
Format: 16 bits
This parameter is used, if necessary, to scale the analog input.
However, this rarely proves necessary since the maximum
input level (100%) automatically corresponds to the maximum
value of the parameter which is assigned to it.
07.17
: Analog input 3 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
Used to invert the input signal.
Disabled (0):
Input signal not inverted.
Enabled (1):
Input signal inverted.
07.18
: Analog input 3 destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This address should contain the number of the parameter
which you wish to assign to AI3. If AI3 is an analog input, only
numerical parameters can be assigned.
If an unsuitable parameter is programmed, the corresponding
input will take the value 0.
07.19
: AO1 analog output 1 source
Adjustment range :
00.00
to
21.51
Factory setting :
04.01
Format: 16 bits
This parameter is used to select the source which you wish to
assign to analog output AO1.
07.20
: AO1 analog output 1 scale
Adjustment range : 0.000 to 4.000
Factory setting : 1.000
Format: 16 bits
Used to scale the analog output.
If
07.75
= «Automatic calibration» (0): When
07.20
= 1.000,
100% of the analog output corresponds to the maximum value
of the adjustment range of the parameter which has been
assigned to it.
If
07.75
= «Manual calibration» (1):
07.20
x 1000 expresses
the calibration of the 10 V (20 mA). For example
07.20
= 2.500
= A source value of 2500 gives 10 V (20 mA) on the analog
output.
07.21
: AO1 analog output mode
Adjustment range : ± 10 V (0), 0-20 mA (1), 4-20 mA (2)
Factory setting : 4-20 mA (2)
Format: 8 bits
Used to define the type of signal on the analog output.
± 10 V (0):
± 10 V voltage output.
0-20 mA (1):
0 to 20 mA current output.
4-20 mA (2):
4 to 20 mA current output.
07.22
to
07.27
:
Not used
07.28
and
07.29
:
Current loop loss on inputs AI2
and AI3
Adjustment range : Active (0) or Lost (1)
Format: 8 bits
These parameters switch to 1 when in 4-20 mA or 20-4 mA
current mode with or without detection of signal loss, the
analog signal changes to less than 3 mA.
07.30
to
07.50
: Not used
07.51
,
07.52
and
07.53
: U, V, W phase
temperature
Adjustment range : 0 to 200°C
Format: 16 bits
07.54
: Rectifier temperature
Adjustment range : 0 to 200°C
Format: 16 bits
CAUTION:
If the product is a POWERDRIVE FX 33T to 50T, the rectifier
temperature measurement is identical to that of the inverter.
07.55
: Control board temperature
Adjustment range : -40 to +125°C
Format: 16 bits
If
07.55
exceeds 60°C, the drive overtemperature alarm
(
10.18
) is activated.
07.56
and
07.57
: Not used
07.58
: Minimum value of AI1
Adjustment range : 0.00 to 1.00
Factory setting : 0.00
Format: 16 bits
For an analog input value of 0, this parameter is used to set the
minimum value of the destination parameter.
Value 0 = (
07.58
x destination parameter max. value) +
destination parameter min. value.
Example: AI1 is assigned to a parameter with an adjustment
range of 0 to 30000. If
07.58
= 0.01, 0 to 100% on AI1
corresponds to 300 to 30000.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...