140
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.17.2 - Explanation of parameters in menu 16
16.01
: Timer 1 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of timer 1.
16.02
: Timer 1 source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the input source for timer relay
1.
Only «bit» type parameters can be assigned to these inputs. If
an unsuitable parameter is addressed, the input will be frozen
at 0.
16.03
: Timer 1 mode select
Adjustment range : ON timer (0) or OFF timer (1)
Factory setting : ON timer (0)
Format: 8 bits
ON timer (0):
The relay is used for on-delay timing. The output changing to
Enabled (1) is delayed in relation to the input changing to 1.
OFF timer (1):
The relay is used for off-delay timing. The output changing to
Disabled (0) is delayed in relation to the input changing to 0.
Note:
Powering-up of the drive is not taken into account as a transition
of the input; the timer is therefore not activated.
16.04
: Timer 1 unit
Adjustment range : Second (0), Minute (1), Hour (2)
Factory setting : Second (0)
Format: 8 bits
Second (0):
The unit of time for the timer relay is the second.
Minute (1):
The unit of time for the timer relay is the minute.
Hour (2):
The unit of time for the timer relay is the hour.
16.05
: Timer 1 value
Adjustment range : 0.0 to 60.0
Factory setting : 0.0
Format: 16 bits
This parameter is used to set the delay period for timer 1. The
unit depends on the setting of
16.04
.
16.06
to
16.08
: Not used
16.09
: Timer 1 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output
for timer 1.
Only «bit» type parameters can be assigned to these outputs.
If an unsuitable parameter is addressed, the output will be
frozen at 0.
16.10
: Not used
16.11
: Timer 2 output
Adjustment range :Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of timer 2.
16.12
: Timer 2 source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the input source for timer relay
2.
Only «bit» type parameters can be assigned to these inputs. If
an unsuitable parameter is addressed, the input will be frozen
at 0.
16.13
: Timer 2 mode select
Adjustment range : ON timer (0) or OFF timer (1)
Factory setting : ON timer (0)
Format: 8 bits
ON timer (0):
The relay is used for on-delay timing. The output changing to
Enabled (1) is delayed in relation to the input changing to 1.
OFF timer (1):
The relay is used for off-delay timing. The output changing to
Disabled (0) is delayed in relation to the input changing to 0.
Note:
Powering-up of the drive is not taken into account as a transition
of the input; the timer is therefore not activated.
16.14
: Timer 2 unit
Adjustment range : Second (0), Minute (1), Hour (2)
Factory setting : Second (0)
Format: 8 bits
Second (0):
The unit of time for the timer relay is the second.
Minute (1):
The unit of time for the timer relay is the minute.
Hour (2):
The unit of time for the timer relay is the hour.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...