ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
10.82
: Special trip n°2
Adjustment range : 0 to 102
Factory setting : 0
Format: 8 bits
Enter the number of the trip * which should or should not be
reset automatically depending on the setting of
10.80
.
10.83
: Special trip n°3
Adjustment range : 0 to 102
Factory setting : 0
Format: 8 bits
Enter the number of the trip * which should or should not be
reset automatically depending on the setting of
10.80
.
10.84
: Special trip n°4
Adjustment range : 0 to 102
Factory setting : 0
Format: 8 bits
Enter the number of the trip * which should or should not be
reset automatically depending on the setting of
10.80
.
10.85
and
10.96
: Not used
10.97
: Alarm status
Adjustment range : 0 to 15
Format: 8 bits
This parameter lists the status of the various drive alarms.
The alarm appears in an orange banner at the top of the MDX-
Powerscreen interface screen.
Value of
10.97
Function
Equivalent
parameter
1
User alarm 1
10.54
2
User alarm 2
10.55
3
User alarm 3
10.56
4
User alarm 4
10.57
5
Braking resistor
overheating
10.12
6
Motor overload
10.17
7
Drive over temperature
10.18
8
Microcontroller
overoccupancy
9
Rectifier
10
Emergency operation
11
Autocal: measured
inductance
12
Autocal: measured EMF
13
Autocal: no offset on this
encoder
14
Reserved
15
Reserved
16
Reserved
* See the list of trips for parameters
10.20
to
10.29
.
10.98
: Drive status
Adjustment range :0 to 37
Format: 8 bits
This parameter defines the drive operating status.
This information about the drive status is also available on the
two digits on the control board.
(see explanations in Section 7)
Value
Name
Meaning
0
DISABLED
Disabled
1
ENABLED M
Enabled, motor (on load)
2
ENABLED G
Enabled, generator (driving
load)
3
RAMP STOP >M
Stop on ramp, clockwise,
motor
4
RAMP STOP >G
Stop on ramp, clockwise,
generator
5
RAMP STOP <M
Stop on ramp, counter-
clockwise, motor
6
RAMP STOP <G
Stop on ramp, counter-
clockwise, generator
7
TLSP STOP >M
Stop by low-frequency
current injection, clockwise,
motor
8
TLSP STOP >G
Stop by low-frequency
current injection, clockwise,
generator
9
TLSP STOP <M
Stop by low-frequency
current injection, counter-
clockwise, motor
10
TLSP STOP <G
Stop by low-frequency
current injection, counter-
clockwise, generator
11
INDEX STOP >M
Indexed stop
Clockwise, motor
12
INDEX STOP >G
Indexed stop
Clockwise, generator
13
INDEX STOP <M
Indexed stop
Counter-clockwise, motor
14
INDEX STOP <G
Indexed stop
Counter-clockwise,
generator
15
DC Inject.>M
DC injection, clockwise,
motor
16
DC Inject.>G
DC injection, clockwise,
generator
17
DC Inject.<M
DC injection, counter-
clockwise, motor
18
DC Inject.<G
DC injection, counter-
clockwise, generator
19
I LIMIT >M
Current limit, clockwise,
motor
20
I LIMIT >G
Current limit, clockwise,
generator
21
I LIMIT <M
Current limit, counter-
clockwise, motor
22
I LIMIT <G
Current limit, counter-
clockwise, generator
23
DC BUS Lim>M
BUS voltage limit, clockwise,
motor
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...