20
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
Parameter Address
Name
Adjustment range
Factory setting
I/O.06
08.21
DI1 input destination
None
Bit 0 Reference selection using digital inputs
Bit 0 Preset reference selection
using digital inputs
Run forward
Jog
Run reverse
FWD/Reverse
Run/Stop
Stop
Drive reset
Motorised potentiometer up
Motorised potentiometer down
Motorised potentiometer reset
None
I/O.07
08.22
DI2 input destination
Bit 0 Reference
selection using
digital inputs
I/O.08
08.23
DI3 input destination
Bit 0 Preset
reference
selection using
digital inputs
I/O.09
08.24
DI4 input destination
Run forward
I/O.10
08.25
DI5 input destination
Run reverse
I/O.11
08.26
DO1 digital output source
None
Zero speed
At speed
Nominal load reached
Motor overtemperature alarm
Vmax alarm
Brake release
Comparator 4 output
Comparator 5 output
Zero speed
I/O.12
08.28
Output relay 2 source
Vmax alarm
• Apl MENU: ADDITIONAL SETTINGS 1, if Ctr.01 = Centrifugal application
Parameter Address
Name
Adjustment range
Factory setting
Apl.01
09.21
Motorised potentiometer mode
Reset/Enable
Previous/Enable
Reset/Disable
Previous/Disable
Min. Ref/Enable
Min. Ref/Disable
Reset/Disable
Apl.02
09.23
Motorised potentiometer rate
0 to 250 s
20 s
Apl.03
09.24
Motorised potentiometer scale factor
0.00 to 2.50
1.00
Apl.04
09.25
Motorised potentiometer destination
None
Preset ref. 1
Preset ref. 2
Preset ref. 3
Preset ref. 4
None
Apl.05
12.74
Comparator 4 threshold
0.00 to 60000.00
0.00
Apl.06
12.77
Comparator 4 output destination
None
User trip 1
User trip 2
User trip 3
User trip 4
None
Apl.07
12.78
Comparator 4 masking
0.0 to 255.0 s
30.0 s
Apl.08
12.84
Comparator 5 threshold
0.00 to 60000.00
200.00
Apl.09
12.87
Comparator 5 output destination
None
User trip 1
User trip 2
User trip 3
User trip 4
None
Apl.10
12.88
Comparator 5 masking
0.0 to 255.0 s
30.0 s
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...