48
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
01.38
: Percentage trim
Adjustment range : ± 100.0%
Factory setting : 0.0%
Format: 16 bits
An offset proportional to the selected reference can be added
to this reference.
The multiplication coefficient is determined by the analog input
assigned to
01.38
.
Final ref =
Selected ref. x (01.38 + 100)
100
Selected ref. x (01.38 + 100)
100
01.39
and
01.40
: Not used
01.41
Reference select via digital input (bit 0)
Adjustment range : Ana 1/Preset (0) or Ana 2/Keypad (1)
Format: 8 bits
01.42
Reference select via digital input (bit 1)
Adjustment range : Ana 1/Ana 2 (0) Preset/Keypad (1)
Format: 8 bits
Used to assign the digital inputs to selection of the speed
reference.
01.41
: bit 0
01.42
: bit 1
01.14 01.42 01.41 Value
01.49
Selected reference
0
0
0
1
Analog input 1
0
1
2
Analog input 2
1
0
3
Preset reference
1
1
4
Keypad
01.43
and
01.44
: Not used
01.45
to
01.47
: Preset Ref. selection
Adjustment range: Disabled (0) or Enabled (1)
Format: 8 bits
Used to assign the digital inputs to selection of the preset
references.
01.45
: bit 0
01.46
: bit 1
01.47
: bit 2
01.15 01.47 01.46 01.45 Value
01.50
Selected
reference
0
0
0
0
1
Preset reference 1
(RP1)
0
0
1
2
Preset reference 2
(RP2)
0
1
0
3
Preset reference
(RP3)
0
1
1
4
Preset reference 4
(RP4)
1
0
0
5
Preset reference 5
(RP5)
1
0
1
6
Preset reference 6
(RP6)
1
1
0
7
Preset reference 7
(RP7)
1
1
1
8
Preset reference 8
(RP8)
01.48
: Not used
01.49
: Reference selected indicator
Adjustment range : Analog input 1 (1),
Analog input 2 (2),
Preset reference (3),
Keypad (4)
Format: 8 bits
Indicates the value selected by
01.14
.
01.50
: Preset selected reference indicator
Adjustment range : Preset reference 1 (1) to
Preset reference 8 (8)
Format: 8 bits
Indicates the value selected by
01.15
.
01.51
: Power-up keypad control mode reference
Adjustment range : Reset to 0 (0), Last value (1), Preset 1 (2)
Factory setting : Reset to 0 (0)
Format: 8 bits
Reset to 0 (0):
On power-up, the speed reference coming from the parameter-
setting interface is reset to zero.
Last value (1):
On power-up, the speed reference coming from the parameter-
setting interface retains the value it had before power-down.
Preset 1 (2):
On power-up, the speed reference coming from the parameter-
setting interface takes the value of preset reference 1 (
01.21
).
01.52
to
01.59
:Not used
01.60
: Pre-offset reference
Adjustment range : ±
01.06
Format: 32 bits
Indicates the value of the selected speed reference before offset.
01.61
to
01.78
:Not used
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...