146
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
17.06
: Power module test result
Adjustment range : Processing (0), Passed (1), Error U phase (2), Error V phase (3), Error W phase (4), Error rectifier (5),
Error motor (6), Error U and V phase (7), Error V and W phase (8), Error U and W phase (9),
Error STO not connected (10), None (15)
Format: 8 bits
If
17.06
is not set to «Passed (1)», refer to the table below for more information.
17.06
17.08
Comment/Description of the problem
Processing (0)
-
The test is in progress.
Passed (1)
-
The test has been performed successfully.
Error U phase (2)
Error V phase (3)
Error W phase (4)
00013
00014
00015
- Trip on the IGBT or «Driver» board in the output module U (
17.06
= 2);
V (
17.06
= 3); W (
17.06
= 4)
- Connection problem between boards in the output module U (
17.06
= 2);
V (
17.06
= 3); W (
17.06
= 4)
- Short-circuit between phases at the drive output or motor insulation problem
00004
00005
00008
00009
00001
- No control signal on output module U (
17.06
= 2); V (
17.06
= 3); W (
17.06
= 4)
- Motor cables wrongly connected
00020
00021
00022
- Incorrect reading of the temperature on module U (
17.06
= 2); V (
17.06
= 3); W (
17.06
= 4)
Error rectifier (5)
00017
- Line reactor cables wrongly connected
- DC BUS preloading circuit faulty
- One or both fuses for measuring the DC bus voltage blown
00011 - DC BUS voltage measurement incorrect
- Rectifier module faulty
00007 - DC bus DC voltage measurement incorrect
- DC BUS discharge time too long
00019 - Incorrect rectifier temperature reading.
Motor failure (6):
00012 - Short-circuit between 2 drive output phases
00016 - Short-circuit between one drive output phase and earth
- One of the fuses for measuring the DC bus voltage blown
Error U and V phase (7)
Error V and W phase (8)
Error U and W phase (9)
00010
00002 - Current sensor faulty
00013 - Power supply board malfunction
00023 - Incorrect reading of the temperature on module U (
17.06
= 2); V (
17.06
= 3);
W(
17.06
= 4)
Error STO open (10)
00018 The STO inputs are not active. Check that terminals STO1 and STO2 are connected
correctly and restart the test.
None (15)
None
- No test has been performed
- Mains phase missing
- Problem reading the mains voltage on the rectifier bridge
If a problem persists, read the value of
17.08
. Then run a control and interface board test, and note the new values of
17.08
and
17.09
before getting in touch with your usual LEROY-SOMER contact.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...