118
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
11.46
to
11.59
: Not used
11.60
: Drive identification code
Adjustment range : 0 to 32000
Format: 16 bits
This product code gives information on the drive rating, size,
hardware version and variant.
When the nameplate is not visible, this code can be given to
your LEROY-SOMER contact.
11.61
: Advanced menu access code
Adjustment range : 0 to 9999
Factory setting : 149
Format: 16 bits
This parameter is used to limit access to menus 1 to 21 when
setting the parameters via the parameter-setting interface.
If this parameter is not 0, the value of parameter
11.61
must
be entered to enable switching to the advanced menu, such as
for example to switch from the «
Quick setup
» menu to the
«
Advanced setting
» menu.
In factory settings mode, simply enter the value 149 to access
all menus.
11.62
: Not used
11.63
: Standard serial link Timeout
Adjustment range : 0.0 to 25.0 s
Factory setting : 0.0 s
Format: 16 bits
Used to generate the «COM loss» trip if no communication has
taken place within the time period set by this parameter. The
value 0 deactivates monitoring of the communication on the
drive’s P2 connector. The Timeout does not take effect until
one minute after power-up.
11.64
: Save parameters to EEPROM
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
This parameter is used to store in EEPROM the values of drive
parameters that have been changed via the fieldbus.
1) Choose the menu(s) to be saved (
11.65
= 0 to save all
menus)
2) Initiate the save operation,
11.64
= Yes (1)
3) The end of the save operation is indicated by
11.64
changing to No (0).
11.65
: Menu to be saved
Adjustment range : 0 to 21
Factory setting : 0
Format: 8 bits
This parameter is used to choose the menu(s) to be saved
(
11.65
= 0 for all menus)
11.66
: Communication type between drives
Adjustment range :None (0), Inverter of Regen (1),
Rectifier of Regen (2), Twin drive Master (3),
Twin drive Slave (4), Synchro Master (5),
Synchro Slave (6), Encoder Master (7),
Encoder Slave (8)
Factory setting : None (0)
Format: 8 bits
This parameter defines the type of communication to be used
when 2 or more control boards communicate via the dedicated
internal serial link:
None (0):
No communication.
Inverter of Regen (1):
On an MD2R product, select this setting for the inverter
connected to the motor or generator.
Rectifier of Regen (2):
On an MD2R product, select this setting for the inverter which
is connected at the mains supply end.
Twin drive Master (3):
Reserved
Twin drive Slave (4):
Reserved
Synchro Master (5):
Reserved
Synchro Slave (6):
Reserved
Encoder Master (7):
Reserved
Encoder Slave (8):
Reserved
The modification is not taken into account until after the
drive has been powered down.
11.67
: Coder module presence
Adjustment range : No (0), MDX-ENCODER (1),
MDX-RESOLVER (2)
Format: 8 bits
Indicates the presence of an optional sensor feedback module,
connected to the drive.
No (0):
No sensor feedback module.
MDX-ENCODER (1):
Presence of an optional MDX-ENCODER module, connected
to the drive.
MDX-RESOLVER (2):
Presence of an optional MDX-RESOLVER module, connected
to the drive.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...