70
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.6.2 - Explanation of parameters in menu 5
05.01
: Output frequency
Adjustment range : ± 590.00 Hz
Format: 32 bits
Indicates the drive output frequency.
05.02
: Output voltage
Adjustment range : 0 to 999 V
Format: 16 bits
This is the rms voltage at the drive output.
05.03
: Output power
Adjustment range :
±
11.33
x
11.32
x 2,22 x kW
3
1000
±
11.33
x
11.32
x 2,22 x kW
3
1000
Format: 32 bits
(1)
05.03
is the calculated motor active power.
05.03
=
04.01
x
05.02
x (
05.10
x kW).
3
1000
05.03
=
04.01
x
05.02
x (
05.10
x kW).
3
1000
If this parameter has been assigned to an analog output via
menu 7, 10 V corresponds to the maximum power measurable
by the drive (max. drive current = 2.22 x
11.32
).
05.04
: Motor speed
Adjustment range : ± 2 x
01.06
rpm
Format: 32 bits
(1)
The motor speed is calculated from the output frequency
05.01
according to the formula:
05.04
(min
-1
) =
60 x
05.01
number of pairs of motor poles
05.04
(min
-1
) =
60 x
05.01
number of pairs of motor poles
05.05
: DC bus voltage
Adjustment range : 0 to 1300 V
Format: 16 bits
Indicates the DC bus voltage measurement.
05.06
:
Motor rated frequency
Adjustment range : 0.01 to 590.00 Hz
Factory setting : 50.00 Hz
Format: 32 bits
This is the point at which motor operation changes from
constant torque to constant power.
During standard operation, it is the frequency indicated on the
motor nameplate.
05.07
: Motor rated current
Adjustment range : 0.00 to 2.2 x
11.32
Factory setting : 75% x
11.32
Format: 32 bits
This is the value of the motor rated current indicated on the
nameplate. The main purpose of the motor rated current is to
define the motor temperature
04.19
.
(1): Two digits after the decimal point.
05.08
: Motor rated speed
Adjustment range : 0.00 to 60000.00 rpm
Factory setting : 1500.00 rpm
Format: 32 bits
On-load speed of the motor indicated on the nameplate.
Note:
This value must take into account the slip of the asynchronous
motor with respect to the synchronous speed. Under no
circumstances must this slip be negative.
05.09
: Motor rated voltage
Adjustment range : 0 to 999 V
Factory setting : 400 V
Format: 16 bits
Enter the rated voltage indicated on the nameplate taking
account of the normal power supply conditions.
Defines the voltage/frequency ratio as follows:
* If
05.14
= None: Linear U/F law with boost (2) or None:
Square U/F law with boost (5), the boost value is set via
05.15
.
05.10
: Rated power factor
Adjustment range : 0.00 to 1.00
Factory setting : 0.85
Format: 8 bits
The power factor is measured automatically during a level 2
autotune phase (see
05.12
) and stored in this parameter. If it
has not been possible to carry out this autotune procedure,
enter the Cos
ϕ
value indicated on the motor nameplate.
05.11
: Number of motor poles
Adjustment range : Automatic (0), 2 Poles (1), 4 Poles (2),
6 Poles (3), 8 Poles (4), 10 Poles (5),
12 Poles (6), 14 Poles (7), 16 Poles (8)
Factory setting : Automatic (0)
Format: 8 bits
When this parameter is at 0 (Automatic), the drive automatically
calculates the number of poles according to the rated speed
(
05.08
) and the rated frequency (
05.06
). However, the value
can be entered directly in accordance with the table below:
Number of poles
05.11
2
2 Poles (1)
4
4 Poles (2)
6
6 Poles (3)
8
8 Poles (4)
10
10 Poles (5)
12
12 Poles (6)
14
14 Poles (7)
16
16 Poles (8)
Note:
When the number of motor poles is higher than 16, set
05.11
to «Automatic».
Output voltage
Motor speed
05.09
05.54
< 100%
05.54
> 100%
05.15*
05.06
2
05.06
05.54
= 100%
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...