115
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.12.2 - Explanation of parameters in menu 11
11.01
to
11.20
: Assignment of parameters
Apl.01
to
Apl.20
Adjustment range :
00.00
to
21.51
Format: 16 bits
Factory setting : See table below.
These parameters can be used, in order, to assign parameters
Apl.01
to
Apl.20
of the «Quick setup» menu.
Quick setup
menu
Quick setup
assignment
Factory
setting
If
11.43
= 1
(Centrifugal
application)
Factory
setting If
11.43
= 2
(Brake motor
application)
11.01
Apl.01
09.21
12.41
11.02
Apl.02
09.23
12.42
11.03
Apl.03
09.24
12.43
11.04
Apl.04
09.25
12.44
11.05
Apl.05
12.74
12.45
11.06
Apl.06
12.77
12.46
11.07
Apl.07
12.78
12.47
11.08
Apl.08
12.84
03.05
11.09
Apl.09
12.87
00.00
11.10
Apl.10
12.88
00.00
11.11
Apl.11
14.03
00.00
11.12
Apl.12
14.04
00.00
11.13
Apl.13
14.08
00.00
11.14
Apl.14
14.16.
00.00
11.15
Apl.15
14.10
00.00
11.16
Apl.16
14.11
00.00
11.17
Apl.17
14.61
00.00
11.18
Apl.18
14.60
00.00
11.19
Apl.19
00.00
00.00
11.20
Apl.20
00.00
00.00
Note:
If
11.43
is set to «Disabled» (0) or «Other application» (3), the
default value of parameters
11.01
to
11.20
and
Apl.01
to
Apl.20
will be 0.
11.21
and
11.22
: Not used
11.23
: Serial address
Adjustment range : 0 to 247
Factory setting
: 1
Format: 16 bits
Used to define the drive address in the case of control or
supervision via the serial link in MODBUS RTU. Avoid values
containing a zero as they are used to address groups of drives.
Note:
This parameter is used only for the MODBUS RTU link of the
drive’s P2 connector. To configure the MODBUS RTU link of
the MDX-MODBUS option, refer to the manual ref. 4580 of the
MDX-MODBUS option.
11.24
: Serial mode
Adjustment range : LS NET (0), MODBUS RTU (1)
Format: 8 bits
This parameter indicates which protocol is being used for the
current communication on the drive’s P2 connector serial link.
LS NET (0):
LS Net protocol.
MODBUS RTU (1):
MODBUS RTU protocol.
11.25
: Baud rate
Adjustment range : 1200 (0) to 115200 (9)
Factory setting : 19200 (6)
Format: 8 bits
Used to select the data transfer speed for MODBUS RTU.
Speed (baud)
11.25
1200
0
1200
1
1200
2
2400
3
4800
4
9600
5
19200
6
38400
7
57600
8
115200
9
Note:
This parameter is used only for the MODBUS RTU link of the
drive’s P2 connector. To configure the MODBUS RTU link of
the MDX-MODBUS option, refer to the manual ref. 4580 of the
MDX-MODBUS option.
11.26
: Min comms transmit delay
Adjustment range : 0 to 100 ms
Factory setting : 2 ms
Format: 16 bits
As the serial link is 2-wire type, Rx is connected to Tx and Rx\
to Tx\. A communication-related trip may occur if the receiver
responds to a request before the transmitter has had time to
switch. Parameter
11.26
is used to introduce a time between
reception and return of data. After transmission of a request,
the drive needs 1.5 ms before receiving the next command.
The adjustment is made in 2 ms intervals.
Note:
This parameter is used only for the MODBUS RTU link of the
drive’s P2 connector. To configure the MODBUS RTU link of
the MDX-MODBUS option, refer to the manual ref. 4580 of the
MDX-MODBUS option.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...