117
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
11.34 : Drive Ixt function trip threshold
Adjustment range: 30% to 110%
Factory setting: 100%
Format: 8 bits
Parameter
11.34
is used to protect the drive thermally for
specific uses not protected by measuring the temperature of its
modules alone (high switching frequency, etc).
• When the drive output thermal current exceeds
11.34
*
11.32,
parameter
10.19
(drive general warning) is set
to «Yes».
• When the drive output thermal current exceeds
~105%*
11.34
*
11.32,
the drive displays a «Ixt drive overload
trip.
11.35
to
11.42
: Not used
11.43
: Factory settings
Adjustment range : Disabled (0), Centrifugal application (1),
Brake motor application (2), Other application (3)
Factory setting : Disabled (0)
Format: 8 bits
Disabled (0):
When the drive has completed the procedure for returning to
factory settings, 11.43 returns to «Disabled».
Centrifugal application (1):
Return to factory settings of all parameters and adaptation of
the «
Quick setup
» menu to a centrifugal application (quadratic
torque). The «Additional settings 1» Apl menu becomes active
(refer to section 4.2.5).
"Centrifuge application" is not restrictive and also covers
the common applications such as pumps, fans,
compressors, mixers, extruders, crushers
Brake motor application (2):
Return to factory settings of all parameters and adaptation of
the «
Quick setup
» menu to an application with brake motor.
The «Additional settings 2» Apl menu becomes active (refer to
section 4.2.6).
Other application (3):
Return to factory settings of all parameters without adaptation
of the «
Quick setup
» menu. The «Additional settings 1 & 2»
Apl menus are inactive.
Note:
If the proposed configurations are not suitable, the user can
adapt the «Additional settings» Apl menu to his application. In
this case, refer to parameters
11.01
to
11.20
.
11.44
: Not used
11.45
: Motor parameter select
Adjustment range : Motor 1 (0) or Motor 2 (1)
Factory setting : Motor 1 (0)
Format: 8 bits
This parameter is used to select the set of parameters corresponding to the characteristics of motor 1 or 2.
11.45
= 0 (motor 1)
11.45
= 1 (motor 2)
Description
01.06
21.01
Maximum reference clamp
01.07
21.02
Minimum reference clamp
01.14
21.03
Reference selector
02.11
21.04
Acceleration rate 1
02.21
21.05
Deceleration rate 1
05.06
21.06
Motor rated frequency
05.07
21.07
Motor rated current
05.08
21.08
Motor rated speed
05.09
21.09
Motor rated voltage
05.10
21.10
Rated power factor
05.11
21.11
Number of motor poles
05.17
21.12
Stator resistance
05.23
21.13
Voltage offset
05.24
21.14
Motor Transient inductance / Ld
-
21.15
Motor 2 map enable
05.25
21.24
Stator inductance L
s
05.33
21.30
Motor volt per 1000 rpm (Ke)
05.51
21.51
Q axis inductance (synchronous motor)
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...