154
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
18.32
: Rectifier trip validation
Adjustment range: Disabled (0) or Enabled (1)
Factory setting: Enabled (1)
Format: 8 bits
Disabled (0)
: The rectifier trip information has no effect on the
inverter.
Enabled (1):
If
11.66
= «Regen inverter
»
an active rectifier trip
generates a Regen inverter «Rectifier» trip.
NB
:
Available from versions >
5.20
18.33
to
18.34
: Not used
18.35
: DC bus reference filter
Adjustment range: 0 to 10
Factory setting: 0
Format: 8 bits
This parameter is used to insert a filter in the bus voltage
reference, such that:
time constant = 2
18.35
ms.
18.36
to
18.39
: Not used
: Start order for the Regen
Adjustment range: No (0) or Yes (1)
Format: 8 bits
Indicates to the synchronous rectifier the start and stop order
in the case where the start order for the synchronous rectifier
is controlled automatically by the output inverter.
18.40
=
01.11
(inverter start order) or
10.02
(inverter output
activated).
18.41
: Inverter healthy
Adjustment range: No (0) or Yes (1)
Format: 8 bits
Indicates to the input synchronous rectifier that the output
inverter bridge is tripped No (0) or healthy Yes (1).
18.42
: Regen mains alarm
Adjustment range: No (0) or Yes (1)
Format: 8 bits
Information about disappearance of the mains. This information
can be used by the inverter to manage mains supply breaks.
When
18.42
is at «Yes», this information is transmitted to the
inverter bridge to archive the delayed stop mode in parameter
06.03.
18.43
: Reactive current selection mode
Adjustment range: Set by
18.45
(0) or Set by
18.46
(1)
Factory setting: Set by
18.45
(0)
Format: 8 bits
Set by
18.45
(0):
The reactive current of the Regen inverter is set directly by
parameter
18.45
.
Set by
18.46
(1):
The Tg (
ϕ
) (Reactive power/Active power) of the Regen
inverter is set by the value of parameter
18.46
.
18.44
:
Reactive current compensation factor
Adjustment range: ± 20.00%
Factory setting: 0.00%
Format: 16 bits
Used to compensate the reactive current drawn by the mains
filter.
18.45
: Reactive reference current
Adjustment range: ± 100.0%
Factory setting: 0.0%
Format: 16 bits
This parameter is used as the reactive current reference. With a
value of zero, the input power factor is around 1. A value not equal
to zero enables reactive current to be absorbed or produced:
- If the parameter is positive, the absorbed current will lag the
supply voltage
- If the parameter is negative, the absorbed current will lead the
supply voltage
18.46
: Tg (
ϕ
) set point
Adjustment range : -20.000 to 20.000
Factory setting: 0
Format: 16 bits
Depending on the value selected in
18.43
, the value of
18.46
acts as the Tg reference (
ϕ
) at the Regen drive input bridge.
18.47
to
18.49
: Not used
18.50
: Regulated voltage selector
Reserved.
18.51
: Output charge/discharge
Reserved
18.52
: Output voltage (Vout)
Reserved
18.53
: Output voltage set point
Reserved
18.54
: Output voltage max
Reserved
18.55
: Output voltage min
Reserved
18.40
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...