143
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
16.54
to
16.58
: Not used
16.59
: Latch 2 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output of
latching relay 2.
Only «bit» type parameters can be assigned to this output. If an
unsuitable parameter is addressed, the output will be frozen at 0.
16.61
: Latch 3 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of latching relay 3.
16.62
: Latch 3 ON source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the enable source for latching
relay 3. Only a pulse on the input causes the output to change to
Enabled (1).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.63
: Latch 3 OFF source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the disable source for latching
relay 3. A pulse or logic state 1 on the input causes the output to
change to Disabled (0).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.64
to
16.68
: Not used
16.69
: Latch 3 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output of
latching relay 3.
Only «bit» type parameters can be assigned to this output. If an
unsuitable parameter is addressed, the output will be frozen at 0.
16.70
: Not used
16.71
: Latch 4 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of latching relay 4.
16.72
: Latch 4 ON source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the enable source for latching
relay 4. Only a pulse on the input causes the output to change to
Enabled (1).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.73
: Latch 4 OFF source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the disable source for latching
relay 4. A pulse or logic state 1 on the input causes the output to
change to Disabled (0).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.74
to
16.78
: Not used
16.79
: Latch 4 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output of
latching relay 4.
Only «bit» type parameters can be assigned to this output. If an
unsuitable parameter is addressed, the output will be frozen at 0.
16.80
: Number of states timed
Adjustment range : 0 to 8
Factory setting : 0
Format: 8 bits
0:
Scan timer disabled.
1 to 8:
Used to configure the number of scan timer states.
For example, if
16.80
= 3, the scan timer will run a scan
1 --> 2 --> 3 --> 1 ...
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...