5.8.2 - Explanation of parameters in menu 7
Note:
The sampling period is 6 ms for menu 7 inputs and outputs.
07.01
: Analog input 1
Adjustment range :± 100.00%
Format: 16 bits
Used to read the value of the differential analog voltage input
1. This input uses an analog/digital converter with 12-bit
resolution.
07.02
: Analog input 2
Adjustment range :± 100.00%
Format: 16 bits
Used to read the value of the analog current input 2.
This input uses an analog/digital converter with 12-bit resolution.
07.03
: Analog input 3
Adjustment range :± 100.00%
Format: 16 bits
Used to read the non-differential analog input 3. This input
uses an analog/digital converter with 12-bit resolution.
07.04
and
07.05
:
Not used
07.06
: Analog input 1 mode
Adjustment range :0-10 V (0) and ± 10 V (1)
Factory setting : 0-10 V (0)
Format: 8 bits
0-10 V (0):
Receives a voltage signal varying between 0 and +10 V.
± 10 V (1):
Receives a voltage signal varying between -10 V and +10 V.
07.07
: Not used
07.08
and
07.12
: Analog inputs 1 and 2 scaling
Adjustment range : 0.00 to 2.50
Factory setting : 1.00
Format: 16 bits
These parameters are used, if necessary, to scale the analog
inputs. However, this rarely proves necessary since the
maximum input level (100%) automatically corresponds to the
max. value of the destination parameter.
07.09
and
07.13
: Analog inputs 1 and 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert the input signal.
Disabled (0):
Input signal not inverted.
Enabled (1):
Input signal inverted.
07.10
: Analog input 1 destination
Adjustment range :
00.00
to
21.51
Factory setting :
01.36
: Analog reference 1
Format: 16 bits
This address should contain the number of the parameter
which you wish to assign to input AI1.
Only numerical parameters can be assigned.
If an unsuitable parameter is programmed, no assignment will
be taken into account.
07.11
: Analog input 2 mode
Adjustment range:
0-20 mA (0),
20-0 mA (1), 4-20 mA with
detection (2), 20-4 mA with detection (3), 4-20 mA without
detection (4), 20-4 mA without detection (5)
Factory setting : 4-20 mA without detection (4)
Format: 8 bits
Used to define the type of signal connected to the differential
analog input AI2.
If a mode with detection is selected, the drive will cause a «AI2
current loop loss» trip on detection of signal break.
07.14
: Analog input 2 destination
Adjustment range :
00.00
to
21.51
Factory setting :
01.37
: Analog reference 2
Format: 16 bits
This address should contain the number of the parameter
which you wish to assign to input AI2.
Only numerical parameters can be assigned if the input is
configured as an analog input and bit parameters if the input is
configured as a digital input.
If an unsuitable parameter is programmed, no assignment will
be taken into account.
07.15
: AI3 signal type
Adjustment range: 0-20 mA (0), 20-0 mA (1),
4-20 mA with detection (2),
20-4 mA with detection (3),
4-20 mA without detection (4),
20-4 mA without detection (5),
0-10V (6), ± 10 V (7)
Factory setting:
0-10 V (6)
Format: 8 bits
Used to define the type of signal connected to the differential
analog input AI3.
If a mode with detection is selected, the drive will cause a «AI3
current loop loss» trip on detection of signal break.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...