ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
08.21
: DI1 input destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of digital input 1.
Any non-protected «bit» type parameter can be assigned to
the input.
If an unsuitable parameter is addressed, no assignment is
taken into account.
CAUTION:
If
05.70
is set to «Drive terminal (1)» or «2 PTC inputs (3)»,
then digital input DI1 must not be used (do not assign
08.21
).
08.22
: DI2 input destination
Adjustment range :
00.00
to
21.51
Factory setting :
01.45
: Reference selection
Format: 16 bits
This parameter is used to select the destination of digital input 2.
Any non-protected «bit» type parameter can be assigned.
If an unsuitable parameter is addressed to the input or output,
no assignment is taken into account.
08.23
: DI3 input destination
Adjustment range :
00.00
to
21.51
Factory setting :
01.41
: Reference selection
Format: 16 bits
This parameter is used to select the destination of digital input 3.
Any non-protected «bit» type parameter can be assigned.
If an unsuitable parameter is addressed to the input or output,
no assignment is taken into account.
08.24
: DI4 input destination
Adjustment range :
00.00
to
21.51
Factory setting :
06.30
:
FWD/Stop
Format: 16 bits
This parameter is used to select the destination of digital input 4.
Any non-protected «bit» type parameter can be assigned to
the input.
If an unsuitable parameter is addressed, no assignment is
taken into account.
08.25
: DI5 input destination
Adjustment range :
00.00
to
21.51
Factory setting :
06.32
:
Rev/Stop
Format: 16 bits
This parameter is used to select the destination of digital input 5.
Any non-protected «bit» type parameter can be assigned to
the input.
If an unsuitable parameter is addressed, no assignment is
taken into account.
08.26
: DO1 Digital Output source
Adjustment range :
00.00
to
21.51
Factory setting :
10.03
:
Zero speed
Format: 16 bits
This parameter is used to select the source which you wish to
assign to digital output DO1.
Any non-protected «bit» type parameter can be assigned.
If an unsuitable parameter is addressed, no assignment is
taken into account.
08.27
: Output relay 1 source
Adjustment range :
00.00
to
21.51
Factory setting :
10.01
: Drive healthy
Format: 16 bits
This parameter is used to select the source for the output relay.
Any non-protected «bit» type parameter can be assigned.
If an unsuitable parameter is addressed, no assignment is
taken into account.
08.28
: Output relay 2 source
Adjustment range :
00.00
to
21.51
Factory setting :
10.52
: V
max
alarm
Format: 16 bits
This parameter is used to select the source for the output relay.
Any non-protected «bit» type parameter can be assigned.
If an unsuitable parameter is addressed, no assignment is
taken into account.
08.29
: Digital input polarity
Adjustment range : Negative (0) or Positive (1)
Factory setting : Positive (1)
Format: 8 bits
This parameter is used to change the polarity of digital inputs.
Negative (0):
Negative logic.
Positive (1):
Positive logic.
08.30
to
08.49
: Not used
08.50
to
08.53
:
Buffers 1 to 4
Adjustment range : Inactive (0) or Active (1)
Factory setting : Inactive (0)
Format: 8 bits
Binary parameters that can be used as buffer variables.
CAUTION:
At each power-up, parameters
08.50
to
08.53
revert to (0).
08.54
to
08.97
: Not used
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...