135
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
14.63
: PID feedback in user units
Adjustment range : ± 20000.00
Format: 32 bits
This parameter indicates the value of the PID feedback in user
units (scaled using
14.61
).
Parameters
14.62
and
14.63
must appear in the read menu.
14.64
to
14.79
: Not used
14.80
: Curve function output
Adjustment range : ± 20000.00
Format: 32 bits
This parameter indicates the value of the function output.
14.81
: Curve function source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter defines the source parameter for variable to be
processed. Only «numerical» parameters can be assigned. If
an unsuitable parameter is selected, the value of the variable
will be 0.
14.82
: Curve function output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter selects the destination of the variable to be
processed. Only non-protected «non-bit» parameter can be
assigned. If an unsuitable parameter is selected, the value of
the variable taken into account is 0.
14.83
: Not used
14.84
,
14.86
,
14.88
: Abscissas of points
14.90
,
14.92
,
14.94
1 to 8 of the
14.96
,
14.98
curve function
Adjustment range : ± 20000.00
Factory setting : 0.00
Format: 32 bits
14.85
,
14.87
,
14.89
: Ordinates of
14.91
,
14.93
,
14.95
points 1 to 8 of the
14.97
,
14.99
curve function
Adjustment range : ± 20000.00
Factory setting : 0.00
Format: 32 bits
-
14.85
represents the ordinate of abscissa point
14.84
.
-
14.87
represents the ordinate of abscissa point
14.86
.
-
14.89
represents the ordinate of abscissa point
14.88
.
-
14.91
represents the ordinate of abscissa point
14.90
.
-
14.93
represents the ordinate of abscissa point
14.92
.
-
14.95
represents the ordinate of abscissa point
14.94
.
-
14.97
represents the ordinate of abscissa point
14.96
.
-
14.99
represents the ordinate of abscissa point
14.98
.
Description of the function:
- The function is used to generate a curve from a table of x
abscissa points which has a corresponding table of f(x) ordinate
points.
- The points in the table can be in any order.
- Between two consecutive abscissa points, the f(x) ordinate
points are interpolated linearly.
- If the abscissa defined by the source parameter is less than
the smallest abscissa point value of parameters
14.84
to
14.98
, then
14.80
will equal the ordinate corresponding to
the smallest abscissa point value of parameters
14.84
to
14.98
.
- If the abscissa defined by the source parameter is greater than
the largest abscissa point value of parameters
14.84
to
14.98
,
then
14.80
will equal the ordinate corresponding to the largest
abscissa point value of parameters
14.84
to
14.98
.
Note:
The ordinate parameters should be configured in the same
format as the assignment parameters.
CAUTION:
If the curve does not pass through the (0;0) point, you
need to enter all the settings.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...