5.10.2 - Explanation of parameters in menu 9
09.01
: Logic function 1 output
09.02
: Logic function 2 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
Indicate the state of the output of logic functions 1 and 2.
09.03
: Motorised potentiometer reference
Adjustment range : ± 100.0%
Format: 16 bits
Indicates the motorised potentiometer reference level.
09.04
: Logic function 1 source 1
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select source 1 for logic function 1.
Only «bit» type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be frozen
at 0.
09.05
: Logic function 1 source 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert source 1 of logic function 1.
Disabled (0):
Source 1 not inverted.
Enabled (1):
Source 1 inverted.
09.06
: Logic function 1 source 2
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select source 2 for logic function 1.
Only «bit» type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be frozen
at 0.
09.07
: Logic function 1 source 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert source 2 of logic function 1.
Disabled (0):
Source 2 not inverted.
Enabled (1):
Source 2 inverted.
09.08
: Logic function 1 output invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert the output of logic function 1.
Disabled (0):
Output not inverted.
Enabled (1):
Output inverted.
09.09
: Not used
09.10
: Logic function 1 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter defines the internal parameter which will be
assigned by the output of logic function 1.
Only non-protected «bit» type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
09.11
to
09.13
: Not used
09.14
: Logic function 2 source 1
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format : 16 bits
This parameter is used to select source 1 for logic function 2.
Only «bit» type parameters can be used on this input.
If an unsuitable parameter is addressed, the input will be frozen
at 0.
09.15
: Logic function 2 source 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : No (0)
Format: 8 bits
This parameter is used to invert source 1 of logic function 2.
Disabled (0):
Source 1 not inverted.
Enabled (1):
Source 1 inverted.
09.16
: Logic function 2 source 2
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select source 2 for logic function 2.
Only «bit» type parameters can be used on these inputs.
If an unsuitable parameter is addressed, the input will be frozen
at 0.
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...