148
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
17.31
: Minimum supply voltage
Adjustment range : 0 to 999 V
Format: 16 bits
The minimum of the average
17.37
equals 999 after a reset
(
17.29
) so long as no run command is given.
17.32
: Maximum motor current
Adjustment range : 0.00 to 2.2 x
11.32
Format: 32 bits
The maximum of the average
17.40
equals 0 after a reset
(
17.29
) so long as no run command is given.
17.33
: Maximum control board temperature
Adjustment range : 0 to 200°C
Format: 16 bits
The maximum of
17.46
equals 0 after a reset (
17.29
) so long
as no run command is given.
17.34
: Maximum U,V,W phase temperature
Adjustment range : 0 to 200°C
Format: 16 bits
The maximum of the instant value of
17.42
,
17.43
and
17.44
equals 0 after a reset (
17.29
) so long as no run
command is given.
17.35
: Not used
17.36
: Time constant
Adjustment range : 32 ms (0), 64 ms (1), 128 ms (2),
256 ms (3), 512 ms (4), 1 s (5), 2 s (6)
Factory setting : 32 ms (0)
Format: 8 bits
Used to set the time constant of the filter to the average of the
average values given in
17.37
,
17.38
,
17.39
and
17.40
.
17.37
: Average supply voltage
Adjustment range : 0 to 999 V
Format: 16 bits
Average supply voltage at the time of the last drive trip, filtered
by
17.36
.
17.38
: Average DC bus
Adjustment range : 0 to 1300 V
Format: 16 bits
Average bus voltage at the time of the last drive trip, filtered by
17.36
.
17.39
: Average motor speed
Adjustment range : ± 60000 rpm
Format: 32 bits
Average speed filtered by
17.36
at the time of the last trip.
17.40
: Average motor current
Adjustment range : 0 to 2.22 x
11.32
Format: 32 bits
Average motor current at the time of the last trip, filtered by
17.36
.
17.41
: Not used
17.42
: Average U phase temperature
Adjustment range : 0 to 200°C
Format: 16 bits
Average temperature of module U at the time of the last drive
trip, filtered at 128 ms.
17.43
: Average V phase temperature
Adjustment range : 0 to 200°C
Format: 16 bits
Average temperature of module V at the time of the last drive
trip, filtered at 128 ms.
17.44
: Average W phase temperature
Adjustment range : 0 to 200°C
Format: 16 bits
Average temperature of module W at the time of the last drive
trip, filtered at 128 ms.
17.45
: Average rectifier bridge temperature
Adjustment range : 0 to 200°C
Format: 16 bits
Average rectifier temperature at the time of the last drive trip,
filtered at 128 ms.
17.46
: Average control board temperature
Adjustment range : 0 to 200°C
Format: 16 bits
Average temperature of the control board at the time of the last
drive trip, filtered at 128 ms.
17.47
: Not used
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...