32
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
I/O.04
: AO1 analog output 1 source
This parameter is used to select the source you wish to assign
to analog output AO1.
The source can be assigned to the actual motor speed, the
current magnitude, the motor power or the motor active current.
I/O.05
: AO1 analog output 1 scale
This parameter is used to scale the AO1 analog output.
Note:
When
I/O.05
= 1.000, the maximum value of the analog
output corresponds to the maximum value of the parameter
which is assigned to it.
I/O.06
: DI1 input destination
I/O.07
: DI2 input destination
I/O.08
: DI3 input destination
I/O.09
: DI4 input destination
I/O.10
: DI5 input destination
These parameters are used to select the destination for digital
inputs DI1 to DI5.
The destination can be assigned to reference selection by
digital input combination (bit 0), selection of the preset
reference (bit 0), run forward, jog, run reverse, change of
direction of rotation (forward/reverse), run/stop, stop, trip
reset, motorised potentiometer up, motorised potentiometer
down and motorised potentiometer reset.
CAUTION:
If
Mtr.06
is set to «Drive terminal» or «2 PTC inputs», then
digital input DI1 must not be used (do not assign
I/O.06
).
I/O.11
: DO1 digital output source
I/O.12
: Output relay 2 source
These parameters are used to select the source you wish to
assign to digital output DO1 or output relay RL2.
The source can be assigned to zero speed, at speed, nominal
load reached, the motor overtemperature alarm, the maximum
speed alarm, state of the brake control output, comparator 4 or
5 output.
4.2.5 - Additional settings 1, if
Ctr.01
= Centrifugal application
Apl.01
: Motorised potentiometer mode
Reset/Enable:
The reference is reset to 0 on each power-up. The up/down
and reset inputs are active at all times.
Previous/Enable:
On power-up, the reference is at the same level as before power-
down. The up/down and reset inputs are active at all times.
Reset/Disable (#):
The reference is reset to 0 on each power-up. The up/down
inputs are active only when the drive output is active. The reset
input is active at all times.
Previous/Disable:
On power-up, the reference is at the same level as before
power-down. The up/down inputs are only active when the
drive output is active. The reset input is active at all times.
Min. Ref/Enable:
On power-up, the reference value equals the minimum speed
(
Spd.02
). The up/down and reset inputs are active at all times.
Min. Ref/DISABLE:
On power-up, the reference value equals the minimum speed
(
Spd.02
). The up/down inputs are only active when the drive
output is active. The reset input is active at all times.
Apl.02
: Motorised potentiometer rate
This parameter defines the time it takes for the motorised
potentiometer reference to change from 0 to 100.0%.
It will take twice as long to change from -100.0% to +100.0%.
Defines the potentiometer sensitivity.
Apl.03
: Motorised potentiometer scale factor
The maximum value of the motorised potentiometer reference
automatically takes the maximum value of the parameter to
which it is assigned.
This parameter can therefore be used to adapt the maximum
value of the motorised potentiometer reference to the maximum
value required by the application.
Example:
- The up/down reference is addressed to a preset reference
with the adjustment range +
Spd.01
.
- If
Spd.01
= 1500 rpm, so that the maximum value of the up/
down reference corresponds to 1000 rpm:
==>
Apl.03
=
= 0,67
1000
Spd.01
=
= 0,67
1000
Spd.01
Apl.04
: Motorised potentiometer destination
This parameter is used to define the numerical parameter
which the motorised potentiometer reference will control.
Example: The motorised potentiometer reference acts as a
speed reference. The motorised potentiometer reference can
be sent to a preset reference (select for example RP1: Preset
Reference
Spd.04
).
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...