53
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
02.09
: Not used
02.10
: Acceleration rate selector
Adjustment range : Terminal inputs (0), Acceleration rate 1 (1) to
Acceleration rate 8 (8), Related to preset
speed (9)
Factory setting : Acceleration rate 1 (1)
Format: 8 bits
This parameter is used to select the acceleration ramp as
follows:
Terminal inputs (0):
Selection of the acceleration ramp via digital inputs. The choice
of ramp comes from the binary/decimal converter in menu 9
(
09.32
).
Acceleration rate 1 (1) to Acceleration rate 8 (8):
Selection of acceleration ramps 1 to 8.
Related to preset speed (9):
The ramp is automatically associated with the corresponding
preset speed.
Note:
If you are using the binary sum, the value of the offset
09.34
must
at least equal 1 so that
09.32
> 0.
02.11
to
02.18
: Acceleration rates 1 to 8
Adjustment range : 0.1 to 3200.0 s
*
Factory setting : 20.0 s
Format: 16 bits
Sets the time for acceleration from 0 to 1000 rpm
*
.
02.11
to
02.18
=
t(s) x 1000 rpm
(N2 - N1) rpm
t(s) x 1000 rpm
(N2 - N1) rpm
*
02.11
: Acceleration rate 1 (main ramp in factory settings)
02.12
to
02.18
: Acceleration rate 2 to Acceleration rate 8
02.19
: Jog acceleration rate
Adjustment range : 0.1 to 3200.0 s
*
Factory setting : 0.2 s
Format: 16 bits
Sets the time for acceleration from 0 to 1000 rpm
*
.
02.19
=
t(s) x 1000 rpm
(N2 - N1) rpm
t(s) x 1000 rpm
(N2 - N1) rpm
*
02.20
: Deceleration rate selector
Adjustment range : Terminal inputs (0), Deceleration rate 1 (1) to
Deceleration rate 8 (8), Related to preset
speed (9)
Factory setting : Deceleration rate 1 (1)
Format: 8 bits
This parameter is used to select the deceleration ramp as
follows:
Terminal inputs (0):
Selection of the deceleration ramp via digital inputs. The choice
of ramp comes from the binary/decimal converter in menu 9
(
09.32
).
Deceleration rate 1 (1) to Deceleration rate 8 (8):
Selection of deceleration ramps 1 to 8
Related to preset speed (9):
The ramp is automatically associated with the corresponding
preset speed.
Note:
If you are using the binary sum, the value of the offset
09.34
must
at least equal 1 so that
09.32
> 0.
02.21
to
02.28
:
Deceleration rates 1 to 8
Adjustment range : 0.1 to 3200.0 s
*
Factory setting : 20.0 s
Format: 16 bits
Sets the time for deceleration from 1000 rpm
*
to 0.
02.21
to
02.28
=
t(s) x 1000 rpm
(N2 - N1) rpm
t(s) x 1000 rpm
(N2 - N1) rpm
*
02.21
: Deceleration rate 1 (main ramp in factory settings)
02.22
to
02.28
: Deceleration rate 2 to Deceleration rate 8
* Note:
The reference speed can be changed from 1000 to 100
min
-1
using parameter
02.56
. This makes it possible to multiply
the acceleration and deceleration times by 10.
N (rpm)
1000
N2
N1
0
Value of
02.11
to
02.18
t
t (s)
0
Value of
02.21
to
02.28
t
t (s)
N (rpm)
1000
N2
N1
0
Value of
02.19
t
t (s)
N (rpm)
1000
N2
N1
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...