147
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
17.07
: Not used
17.08
: Error code 1
Adjustment range : 0 to 65535
Format: 16 bits
An internal code, for more accurately determining the problems
on the control and interface board or power test. Make a note
of this before getting in touch with your usual LEROY-SOMER
contact.
17.09
: Error code 2
Adjustment range : 0 to 65535
Format: 16 bits
An internal code, for more accurately determining the problems
on the control and interface board test. Make a note of this
before getting in touch with your usual LEROY-SOMER
contact.
17.10
: Not used
17.11
: Status preceding 17.12 status
Adjustment range : 0 to 37 (see
10.98
)
Format: 8 bits
This is the drive status before the trip.
17.12
: Status at
fault
Adjustment range : 0 to 37 (see
10.98
)
Format: 8 bits
This is the drive status at the time of the trip.
17.13
: Time between states
Adjustment range : 0.000 to 6000.000 s
Format: 32 bits
Indicates the time that has elapsed between drive states
17.11
and
17.12
. This time is a multiple of 2 ms. If the
parameter displays 6000,000 s, this indicates that the elapsed
time exceeds the display capacity.
17.14
to
17.17
: Not used
17.18
and
17.19
: Counter duration fault - 1
Adjustment range : 0.000 to 9.364 (a, j) (
17.18
)
Adjustment range : 00.00 to 23.59 (h, m) (
17.19
)
Format: 16 bits
17.20
and
17.21
: Counter duration fault - 2
Adjustment range : 0.000 to 9.364 (a, j) (
17.20
)
Adjustment range : 00.00 to 23.59 (h, m) (
17.21
)
Format: 16 bits
17.22
and
17.23
: Counter duration fault - 3
Adjustment range : 0.000 to 9.364 (a, j) (
17.22
)
Adjustment range : 00.00 to 23.59 (h, m) (
17.23
)
Format: 16 bits
17.24
and
17.25
: Counter duration fault - 4
Adjustment range : 0.000 to 9.364 (a, j) (
17.20
)
Adjustment range : 00.00 to 23.59 (h, m) (
17.25
)
Format: 16 bits
17.26
and
17.27
: Counter duration fault - 5
Adjustment range : 0.000 to 9.364 (a, j) (
17.26
)
Adjustment range : 00.00 to 23.59 (h, m) (
17.27
)
Format: 16 bits
These counters indicate the operating time since the drive was
first commissioned until the occurrence of trip -5 (see
06.22
and
06.23
).
Note:
Trip -5 corresponds to the trip displayed in
10.24
.
17.28
: Not used
17.29
: Reset of measured maximum
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
No (0):
Values of parameters
17.30
to
17.34
not reset.
Yes (1):
Values of parameters
17.30
to
17.34
are reset.
17.30
: Maximum supply voltage
Adjustment range : 0 to 999 V
Format: 16 bits
The maximum of the average
17.37
equals 0 after a reset
(
17.29
) so long as no run command is given.
Speed
Time
10.98 =
Disabled
10.98 =
Enabled M
10.98 =
Stop on Ramp>M
10.98 =
Disabled
17.13
Drive trip
17.11
17.12
Содержание LEROY-SOMER Powerdrive FX
Страница 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Страница 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 49: ...49 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 95: ...95 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 131: ...131 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e 5 14 MENU 13 Reserved...
Страница 137: ...137 ADVANCED PARAMETER SETTING MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Страница 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...