12 - 26
12. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J3-350A4 MR-J3-500A(4) MR-J3-700A(4)
Always remove the wiring (across P-C) of the servo amplifier built-in regenerative resistor and fit the
regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option
overheats abnormally.
(Note 2)
P
C
G3
G4
P
C
Always remove wiring (across P-C) of servo
amplifier built-in regenerative resistor.
Cooling fan(Note 1)
Servo amplifier
Regenerative option
5m or less
Note 1. When using the MR-RB51 MR-RB3G-4, MR-RB5G-4, MR-RB34-4 or MR-RB54-4, forcibly cool
it with a cooling fan (1.0m
3
/min, 92 or so).
2. Make up a sequence which will switch off the magnetic contactor (MC)
when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative resistor
terminals (across P-C), fit them back to back, and secure them to the frame with the accessory screw as
shown below.
Mounting method
Accessory screw