12 - 64
12. OPTIONS AND AUXILIARY EQUIPMENT
12.12 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
No-fuse breaker
Fuse
Servo amplifier
Not using power
factor improving
reactor
Using power factor
improving reactor
(Note) Class
Current [A]
Voltage
AC [V]
Magnetic
contactor
MR-J3-10A (1)
30A frame 5A
30A frame 5A
K5
10
MR-J3-20A
30A frame 5A
30A frame 5A
K5
10
MR-J3-20A1
30A frame 10A
30A frame 10A
K5
15
MR-J3-40A
30A frame 10A
30A frame 5A
K5
15
MR-J3-60A 70A 100A 40A1
30A frame 15A
30A frame 10A
K5
20
S-N10
MR-J3-200A
30A frame 20A
30A frame 15A
K5 40
S-N18
MR-J3-350A
30A frame 30A
30A frame 30A
K5
70
S-N20
MR-J3-500A
50A frame 50A
50A frame 40A
K5
125
S-N35
MR-J3-700A
100A frame 75A
50A frame 50A
K5
150
S-N50
MR-J3-11KA
100A frame 100A
100A frame 75A
K5
200
S-N65
MR-J3-15KA
225A frame 125A 100A frame 100A
K5 250
S-N95
MR-J3-22KA
225A frame 175A 225A frame 150A
K5 350
250
S-N125
MR-J3-60A4
30A frame 5A
30A frame 5A
K5 10
MR-J3-100A4
30A frame 10A
30A frame 10A
K5 15
MR-J3-200A4
30A frame 15A
30A frame 15A
K5 25
S-N10
MR-J3-350A4
30A frame 20A
30A frame 20A
K5 35
MR-J3-500A4
30A frame 30A
30A frame 30A
K5 50
S-N18
MR-J3-700A4
50A frame 40A
50A frame 30A
K5 65
S-N20
MR-J3-11KA4
60A frame 60A
50A frame 50A
K5 100
S-N25
MR-J3-15KA4
100A frame 75A
60A frame 60A
K5 150
S-N35
MR-J3-22KA4
225A frame 125A 100A frame 100A
K5 175
600
S-N65
Note. This servo amplifier is UL/C-UL-listed when using a Class T fuse. Therefore, when using the servo amplifier as a UL/C-UL
Standard compliant product, be sure to use the Class T fuse.