CHAPTER 15 TROUBLESHOOTING
15
15.
5
List
of
E
rrors
Parameter
963
Stop group 2 sudden stop
selection error
■
Description
The set value of the detailed parameter 2 "Stop
group 2 sudden stop selection" is outside the
setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 57
Axis 2: 207
Axis 3: 357
Axis 4: 507
■
Setting range
0, 1
964
Stop group 3 sudden stop
selection error
■
Description
The set value of the detailed parameter 2 "Stop
group 3 sudden stop selection" is outside the
setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 58
Axis 2: 208
Axis 3: 358
Axis 4: 508
■
Setting range
0, 1
966
Outside allowance
circular interpolation error
width
■
Description
The set value of the detailed parameter 2
"Allowance circular interpolation error width" is
outside the setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 60, 61
Axis 2: 210, 211
Axis 3: 360, 361
Axis 4: 510, 511
■
Setting range
0 to 10000
967
External command
function selection error
■
Description
The set value of the detailed parameter 2 "External
command function selection" is outside the setting
range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 62
Axis 2: 212
Axis 3: 362
Axis 4: 512
■
Setting range
0, 1, 2, 3
980
OPR method error
■
Description
The set value of the OPR basic parameter "OPR
method" is outside the setting range.
■
Operation status at error occurrence
The LD75 READY signal (X0) does not turns ON.
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 70
Axis 2: 220
Axis 3: 370
Axis 4: 520
■
Setting range
0, 1, 2, 3, 4, 5
Classification
of errors
Error
code
Error name
Operation status at error occurrence
Action/Related buffer memory address/Set
range (Setting with program)
Содержание MELSEC-L LD75D
Страница 1: ...MELSEC L LD75P LD75D Positioning Module User s Manual LD75P1 LD75P2 LD75P4 LD75D1 LD75D2 LD75D4 ...
Страница 2: ......
Страница 11: ...9 Memo ...
Страница 47: ...45 CHAPTER 2 SYSTEM CONFIGURATION 2 2 1 General Image of System 1 When connected to a CPU module ...
Страница 176: ...174 ...
Страница 264: ...262 ...
Страница 266: ...264 ...
Страница 267: ...265 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 268: ...266 ...
Страница 269: ...267 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 270: ...268 ...
Страница 271: ...269 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 272: ...270 Z ABRST1 instruction execution ...
Страница 273: ...271 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 278: ...276 ...
Страница 279: ...277 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 280: ...278 ...
Страница 281: ...279 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 282: ...280 ...
Страница 283: ...281 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 284: ...282 ...
Страница 285: ...283 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 286: ...284 ...
Страница 287: ...285 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 316: ...314 Memo ...
Страница 685: ...683 APPENDICES A Appendix 1 Function Update Appendix 1 1 Function comparison Memo ...
Страница 738: ...736 Memo ...
Страница 806: ...804 5 LD75D2 Unit mm 6 LD75D4 Unit mm 45 4 90 4 95 4 45 45 DIN rail center 45 4 90 4 95 4 45 45 DIN rail center ...
Страница 817: ......