672
Parameter
958
JOG deceleration time
selection setting error
■
Description
The set value of the detailed parameter 2 "JOG
deceleration time selection setting" is outside the
setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 51
Axis 2: 201
Axis 3: 351
Axis 4: 501
■
Setting range
0, 1, 2, 3
959
Acceleration/deceleration
process selection setting
error
■
Description
The set value of the detailed parameter 2
"Acceleration/deceleration process selection
setting" is outside the setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 52
Axis 2: 202
Axis 3: 352
Axis 4: 502
■
Setting range
0, 1
960
S-curve ratio setting error
■
Description
The set value of the detailed parameter 2 "S-curve
ratio" is outside the setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 53
Axis 2: 203
Axis 3: 353
Axis 4: 503
■
Setting range
1 to 100
961
Illegal sudden stop
deceleration time
■
Description
The set value of the detailed parameter 2 "Sudden
stop deceleration time" is outside the setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 54, 55
Axis 2: 204, 205
Axis 3: 354, 355
Axis 4: 504, 505
■
Setting range
1 to 8388608
962
Stop group 1 sudden stop
selection error
■
Description
The set value of the detailed parameter 2 "Stop
group 1 sudden stop selection" is outside the
setting range.
■
Operation status at error occurrence
At start: The system will not operate.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 Sudden stop selection (stop group 3).
(Note that the deceleration stop only occurs during
the manual pulse generator operation.)
■
Action
With the setting brought into the setting range,
turn the PLC READY signal [Y0] from OFF to ON.
■
Buffer memory address
Axis 1: 56
Axis 2: 206
Axis 3: 356
Axis 4: 506
■
Setting range
0, 1
Classification
of errors
Error
code
Error name
Operation status at error occurrence
Action/Related buffer memory address/Set
range (Setting with program)
Содержание MELSEC-L LD75D
Страница 1: ...MELSEC L LD75P LD75D Positioning Module User s Manual LD75P1 LD75P2 LD75P4 LD75D1 LD75D2 LD75D4 ...
Страница 2: ......
Страница 11: ...9 Memo ...
Страница 47: ...45 CHAPTER 2 SYSTEM CONFIGURATION 2 2 1 General Image of System 1 When connected to a CPU module ...
Страница 176: ...174 ...
Страница 264: ...262 ...
Страница 266: ...264 ...
Страница 267: ...265 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 268: ...266 ...
Страница 269: ...267 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 270: ...268 ...
Страница 271: ...269 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 272: ...270 Z ABRST1 instruction execution ...
Страница 273: ...271 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 278: ...276 ...
Страница 279: ...277 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 280: ...278 ...
Страница 281: ...279 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 282: ...280 ...
Страница 283: ...281 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 284: ...282 ...
Страница 285: ...283 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 286: ...284 ...
Страница 287: ...285 CHAPTER 6 PROGRAM USED FOR POSITIONING CONTROL 6 6 4 Positioning Program Examples ...
Страница 316: ...314 Memo ...
Страница 685: ...683 APPENDICES A Appendix 1 Function Update Appendix 1 1 Function comparison Memo ...
Страница 738: ...736 Memo ...
Страница 806: ...804 5 LD75D2 Unit mm 6 LD75D4 Unit mm 45 4 90 4 95 4 45 45 DIN rail center 45 4 90 4 95 4 45 45 DIN rail center ...
Страница 817: ......