8. Spindle Parameters
8.3 MDS-B-SP/SPH, MDS-C1-SP/SPH
II - 250
No. Items
Details
Setting
range
Standard
setting
3280
SP080
Use not possible.
0
0
3281
SP081 LMCA
3282
SP082 LMCB
3283
SP083
Fixed control
constant
This is used by Mitsubishi.
Set to "0" unless particularly designated.
0 0
3284
to
3286
SP084
to
SP086
Use not possible.
0
0
3287
(PR)
SP087 DIQM Target value of
variable torque
limit magnifica-
tion at
deceleration
Set the minimum value of variable torque
limit at deceleration.
0 to 150
(%)
75
3288
(PR)
SP088 DIQN Speed for starting
change of
variable torque
limit magnifica-
tion at
deceleration
Set the speed where the torque limit value at
deceleration starts to change.
SP088
SP017
100%
SP087
Torque limit
Inversely proportional
to speed
0 to 32767
(r/min)
3000
3289
SP089
Use not possible.
0
0
3290
SP090
Use not possible.
0
0
3291 SP091 OFSN Motor
PLG
forward rotation
offset compensa-
tion
Set the PLG offset value for the forward
rotation.
Normally set to "0".
-2048 to
2047
(-1mv)
0
3292 SP092 OFSI Motor
PLG
reverse rotation
offset compensa-
tion
Set the PLG offset value for the reverse
rotation.
Normally set to "0".
-2048 to
2047
(-1mv)
0
3293
(PR)
SP093 ORE
Tolerable pulse
check error
Set this when detecting the pulse detector's
pulse mistakes.
(Valid only for full close control.)
0 to 32767 0
3294
(PR)
SP094 LMAV Load meter
output filter
Set the filter time constant of load meter
output.
When "0" is set, a filter time constant is set to
100ms.
0 to 32767
(2ms)
0
3295
(PR)
SP095 VFAV Fixed control
constant
Set by Mitsubishi.
Set "0" unless designated in particular.
0 0