4.3.2 Control Circuit Cable Size and Tightening Torque
Select the cable according to Table 4.3.2.1 and 4.3.3.2. Use crimp ferrules on the cable ends for
simpler and more reliable wiring.
Table 4.3.2.1 Cable Size and Tightening Torque (<5.5kW models)
Terminal
Screw
Size
Tightening
Torque
Nm
( lb.in.)
Bare Cable
Ferrule-Type Terminal
Cable Type
Applicable
Size
mm2
( AWG)
Suggeste
d Size
mm2
( AWG)
Applicable
Size
mm2
( AWG)
Suggeste
d Size
mm2
( AWG)
10V, A2, AC, AM, D1, DC,
COM, 24V, SC, S1, S2, S3, S4,
PE
M2.5
0.4
(3.52)
0.13 ~ 2.08
(26 ~ 14)
0.13
(26)
0.41 ~ 1
(17 ~ 21)
0.41
(17)
Shielded
cable, etc.
R1A, R1B, R1C
M2.5
0.57
(5)
0.13 ~ 3.31
(26 ~ 12)
0.13
(26)
3.31 ~ 5.26
(12 ~ 10)
3.31
(12)
Shielded
cable, etc.