87
b5- 05 PID Output Limit
Sets the upper limit of output from PID control as a percentage of the maximum frequency.
No.
Name
Setting Range
Default
b5-05
PID Output Limit
0.0 to 100.0%
100.0%
b5- 06 PID Bias Voltage Adjustment
Sets the PID bias voltage adjustment as a percentage of the maximum frequency to add to the
PID control output.
No.
Name
Setting Range
Default
b5-06
PID Bias Voltage Adjustment
-100.0 to 100.0%
0.0%
b5- 07 PID Primary Delay Time
Sets the delay time for the PID output filter. Change is normally not required.
No.
Name
Setting Range
Default
b5-07
PID Primary Delay Time
0.00 to 10.00 s
0.00 s
Note: This parameter is effective to avoid the vibration when abrasion is high and rigidity is low. Increasing this
delay time could reduce the response of the drive.
b5- 08 PID Output Reverse
Sets the reverse for the PID output and decision for the relationship between the target and
feedback
No.
Name
Setting Range
Default
b5-08
PID Output Reverse
0, 1
0
0 : Normal PID Output
A positive PID input causes an increase in the PID output.
1 : Reverse PID Output
A positive PID input causes an decrease in the PID output.
b5- 09 PID Output Gain
Sets a gain to multiply by the PID output. The compensation will be more effective when
b5-00=3 or 4.
No.
Name
Setting Range
Default
b5-09
PID Output Gain
0.00 to 25.00
1.00
b5- 10 PID Output Reverse Selection
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...