145
Open
The motor runs in the forward direction
Closed
The motor runs in the reverse direction
Output
frequency
Forward Run
command
Reverse Run
command
During
reverse
OFF
ON
Time
Figure 6.59 During Reverse Operation
23: Retain
24: During Regeneration
When the motor outputs during regeneration, the assigned output terminal closes.
25 : During Restart
When the drive attempts to clear a fault during restart, the assigned output terminal closes. If
the fault is cleared after restart, the output terminal opens. If the number of restart attempt
reaches the number set to P5-00 (Number of Auto Restart Attempts) without clearing a fault
successfully, the output terminal opens after the fault is triggered.
26 : Motor Overload Pre-Alarm (oL1)
When the motor overload level exceeds 90% of the detection level, the assigned output
terminal closes. Refer to P1-00 (Motor Protection Function Selection) for details.
27 : Drive Overheat Pre-Alarm (oH)
When the drive heatsink temperature exceeds the oH (overheat) detection level, the assigned
output terminal closes.
28 : Retain
29 : Mechanical Weakening Detection (Normal Open)
When the mechanical weakening situation is detected, the assigned output terminal closes.
30~34 : Retain