142
When the drive is ready to run or during run, the output terminal closes. According to the
conditions listed below, when a fault occurs or the drive cannot run even if a Run command is
entered, the output terminal closes.
·
When the power is cut off
·
During a fault
·
When the internal power supply of the drive malfunctions
·
When an improper parameter setting makes the drive unable to run
·
An overvoltage or undervoltage fault is triggered during stop
·
When setting a parameter in the programming mode
5 : Uv (Undervoltage) Detection
When the main circuit DC voltage falls below the Uv detection level, the output terminal closes.
The Uv detection level is set in P2-03.
Terminal
Description
Open
The main circuit voltage is higher than the P2-03 level
Closed
The main circuit voltage is lower than the P2-03 level
6 : During Baseblock
During baselock, the output terminal closes and the output transistors do not switch.
Terminal
Description
Open
The drive is not performing baseblock
Closed
The drive is performing baseblock
7: Retain
8 : Frequency Command Source
Displays the currently selected frequency command source.
Terminal
Description
Open
Frequency command is provided from external command 1 (b1-00) or 2 (b1-07)
Closed
Frequency command is provided from the drive keypad
9 : Frequency Command Loss
When a frequency command loss is detected, the assigned output terminal closes. Refer to
P4-02 (Frequency Command Loss Detection Selection) for details.
10: Run Command Source
Displays the currently selected Run command source.
Terminal
Description