158
Setting
Function
0
Frequency Command
1
Output Frequency
2
Output Current
3
Motor Speed
4
Output Voltage
5
DC Voltage
6
Output Power
7
Retain
8
AI1 Input
9
AI2 Input
10
Soft Starter Output Frequency
11
Pulse Train Input
E4- 02/ E4- 03
Terminal FM Monitor Gain / Voltage Bias
E4- 06/ E4- 07
Terminal AM Monitor Gain / Voltage Bias
E4-02/ E4-06 Sets the gain for terminal FM and AM as a percentage.
E4-03/ E4-07 Sets the voltage bias for terminal FM and AM as a percentage.
10 V equals 100% when setting E4-02, E4-03, E4-06 and E4-07. Figure 6.69 illustrates the gain
and bias operation.
No.
Name
Setting Range
Default
E4-02
Terminal FM Monitor Gain
-999.9 to 999.9%
100.0%
E4-03
Terminal FM Voltage Bias
-999.9 to 999.9%
0.0%
E4-06
Terminal AM Monitor Gain
-999.9 to 999.9%
100.0%
E4-07
Terminal AM Voltage Bias
-999.9 to 999.9%
0.0%
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...