147
When a PID Feedback Low is detected, the assigned output terminal closes. When the PID
feedback value falls below the b5-12 level for longer than the time set to b5-13, the fault will
be detected. Refer to b5-11 on page 79
41 :PID Feedback High
When a PID Feedback High is detected, the assigned output terminal closes. When the PID
feedback value exceeds the b5-22 level for longer than the time set to b5-23, the fault will be
detected. Refer to b5-11 on page 79?
42 : During KEB Operation
The assigned output terminal closes during KEB operation. Refer to “KEB function”on page
187?
43 : Retain
44 : During Fast Stop
The assigned output terminal closes during a fast stop. Refer to setting 21 and 22 (Fast Stop)
of multi-function Digital Inputs.
45 : Retain.
When the internal cooling fan alarm is triggered, the assigned output terminal closes.
46 :Rotor Position Detection Complete
After the Run command is given and the rotor position detection is complete, the assigned
terminal closes.
47:Retain
48:Retain
49:Brake Control
If E2-00 ~ E2-03 (Multi-Function Digital Output) is set to 49 (the brake control), when the run
command is ON and inverter output frequency
≥
P4-05 (mechanical brake release frequency),
the terminal is closed until the when the inverter operation command is OFF and the output
frequency
≤
P4-06 (mechanical brake operation frequency), the terminal is disconnected
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...