105
C6 Carrier Frequency
C6-00
Carrier Frequency Selection
Sets the switching frequency of the drive output transistors. Adjust this setting to reduce
audible noise and leakage current.
Note:
1.
If this level is set higher than the default setting, the drive rated current will be decreased. Refer to Table 6.11 on
page 107.
2.
The default setting is 2 in PM motor control, 8 (8kHz) in IM motor HD mode and 2 (2kHz) in IM motor ND mode.
No.
Name
Setting Range
Default
C6-00
Carrier Frequency Selection
0 to 16
Determined by A1-02 and o2-03. Once
A1-06 is redefined, the default will be
changed accordingly
C6-00
Carrier Frequency
C6-00
Carrier Frequency
C6-00
Carrier Frequency
0
Determined by C6-01
to C6-03
6
6 kHz
12
12kHz
1
Retain
7
7 kHz
13
13 kHz
2
2 kHz
8
8 kHz
14
14kHz
3
3 kHz
9
9 kHz
15
15kHz
4
4 kHz
10
10 kHz
16
16kHz
5
5 kHz
11
11 kHz
Setting Carrier Frequency
Situation
Solution
Speed and torque fluctuate at low speeds
Lower the carrier frequency
The drive noise affects peripheral devices
Excessive leakage current from the drive
Cable connecting the drive and motor is too
long<1>
Loud noise from the motor
Increase the carrier frequency <2>
<1> If the cable is too long, lower the carrier frequency according to the follow instructions.
<2> If ND mode is selected in A1-06, the default carrier frequency is 8kHz which is very close to the setting of 2kHz
The carrier frequency can be increased in ND mode. However the higher the setting is, the smaller the current will
be.
Cable Length
Less than 50 m
Less than 100 m
More than 100 m
C6-00
2 to 16 ( excluding 16 kHz )
2 to 5
2
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...