96
b6-00
b6-02
b6-01
b6-03
OFF
ON
OFF
Run
Command
Output
Frequency
Figure 6.21 Dwell Function at Start and Stop
b6- 00 / b6- 01
Dwell Frequency and time at Start
Sets the frequency to b6-00 used to be held for the time set in b6-01 during acceleration.
No.
Name
Setting Range
Default
b6-00
Dwell Frequency at Start
0.0 Hz to <1>
0.0 Hz
b6-01
Dwell time at Start
0.0 to 10.0 s
0.0 s
<1> The upper limit is determined by the values set to d1-02 (Maximum Output Frequency), d1-13 (Motor 2
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit)
b6- 02 / b6- 03
Dwell Frequency and time at Stop
Sets the frequency to b6-02 used to be held for the time set in b6-03 during deceleration.
No.
Name
Setting Range
Default
b6-02
Dwell Frequency at Stop
0.0 to <1>
0.0 Hz
b6-03
Dwell time at Stop
0.0 to 10.0 s
0.0 s
<1> The upper limit is determined by the values set to d1-02 (Maximum Output Frequency),
d1-13 (Motor 2
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit)