77
Frequency command as a single source b1-00 (or b1-07) set of values
1 :Enabled
Frequency command as
B1-00 and b1-07 frequency instruction set of the superposition of two sources of value, the
frequency superimposed b1-00 and b1-07 can not set to the same source, otherwise it will
be tripped OPE13 error, but not in this simulation input limit (when superimposed b1-00
and b1-07 can simultaneously set to 1). Frequency superposition function is valid only in
Remote mode, Local mode is invalid
Note :
b1-00 and b1-07 is set to analog input simultaneously superimposed use, it will be forced
to specify as input source b1-00 of AI1, AI2 as the input source b1-07. If b1-00 and b1-07 are not
all 1, setting b1-09 = 1, E3-01 = 0, E3-07 = 0, it will be tripped OPE07 error
b1- 10 Run Command at Power up
Determines to accept or ignore an active Run command from Remote during power up.
No.
Name
Setting Range
Default
b1-10
Run Command at Power up
0,1
0
0 : Ignore
Drive ignores an active run command during power up.
Note: The LED indicator blinks when there is an active Run command from Remote during power up. The drive can
start only when the Run command is removed and entered again.
1 : Accept
Drive accepts an active Run command from Remote during power up and starts the motor
immediately
WARNING!
The drive will run the motor immediately at power up if there an active Run command from Remote.
Ensure the protection measures are taken and clear all personnel from the electrical connections and the running
machinery prior to switching command sources. Failure to comply could cause serious injury.
b1- 12 Allowing Local/Remote selection during run
No.
Name
Setting Range
Default
b1-12
Allowing Local/Remote selection
during run
0,1
0
0 :Disable
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...