165
E6-08
RS-485 Communication Parity Selection
0 to 11
1
0: 8, N, 2 (MODBUS RTU)
1: 8, N, 1 (MODBUS RTU)
2: 8, E, 1 (MODBUS RTU)
3: 8, O, 1 (MODBUS RTU)
4: 8, N, 2 (MODBUS ASCII)
5: 8, N, 1 (MODBUS ASCII)
6: 8, E, 1 (MODBUS ASCII)
7: 8, O, 1 (MODBUS ASCII)
8: 7, N, 2 (MODBUS ASCII)
9: 7, N, 1 (MODBUS ASCII)
10: 7, E, 1 (MODBUS ASCII)
11: 7, O, 1 (MODBUS ASCII)
E6-09 Communication Error Detection Time
Determines the detection time to trigger the communication error. (This function is disabled
when set to 0)
No.
Name
Setting Range
Default
E6-09
Communication Fault Detection time
0.0 to 10.0 s
0.0 s
E6-10
Transmit Wait Time
Sets the wait time between the drive receiving data and responding data.
No.
Name
Setting Range
Default
E6-10
Transmit Wait Time
5 to 65 ms
5 ms
E6-11
Drive Operation During Communication Error
No.
Name
Setting Range
Default
E6-11
Drive Operation During
Communication Error
0, 1
0
0 : Display CE Alarm Only
The drive continues operation.
1 : Display CE Fault
The drive coasts to stop.