65
5 Press
to display A1-05 setting.
6 Press
or
to set the password. (1234 is an
example)
7 Press
to display A1-05 setting.
8
”LtH”is displayed when entering A1-05 setting.
Table 6.2.2 Password Entering Steps
Step
1 Press
and select A1-04.
2 Press
to enter A1-04 setting. “nULL”is not displayed
anymore as the password has been set.
3 Press
or
to enter the correct password.
(1234
is an example)
4
The display leaves A1-04 setting automatically as the parameters are
unlocked.
A1- 06 ND/HD Selection
The drive has two duty modes for the load characteristics, heavy duty (HD) mode and normal
duty (ND) mode. The drive rated current and overload tolerance will change based on the duty
mode selection. Choose the suitable mode in A1-06 according to the application.
The HD mode provides 150% overload for 1 minute whereas the ND mode provides 120%
overload for 1 minute. Refer to the drive specifications for details.
No.
Name
Setting Range
Default
A1-06
ND/HD Selection
0, 1
0 ( HD)
Table 6.3 Differences between Heavy Duty and Normal Duty
Characteristics
Heavy Duty Rating (HD)
Normal Duty Rating (ND)
A1-06
0
1