100
Closed). The input terminal does not have to be closed continuously to trigger Fast Stop. It will
trigger Fast Stop even if the closure is momentary. Different from the normal deceleration, the
drive cannot be restarted after entering Fast Stop until completing deceleration, remove the
Fast Stop input and cycling the Run command.
If E2-□□ is set to 44 (During Fast Stop), this terminal will close during Fast Stop.
If Fast Stop is the action selected for a fault detection, the Fast Stop time set in this parameter
will be the deceleration time.
No.
Name
Setting Range
Default
C1-08
Fast Stop Time
0.0 to 6000.0 s <1>
10.0 s
<1> The setting range is determined by the C1-09 (Acc./Dec. Time Unit Selection) setting. When C1-09 = 0, the
setting range is 0.00 to 600.00 (second).
Note: A rapid deceleration will trigger an OVD fault and shut off the drive output causing the motor to coast. To
avoid the motor coasting and to ensure the motor stops safely, always set an appropriate time to this parameter.
C1-09
Acc./Dec. Time Unit Selection
Set the time scaling for C1-00 to C1-08.
No.
Name
Setting Range
Default
C1-09
Acc./Dec. Time Unit Selection
0, 1
1
0 : 0. 01s
Sets the acceleration and deceleration times in 0.01 second units. The setting range will be
0.00 to 600.00 seconds. If 600.1 seconds or more is set to any parameter among C1-00 to
C1-08, C1-09 cannot be set to 0.
1 : 0. 1s
Sets the acceleration and deceleration times in 0.1 second units. The setting range will be 0.00
to 6000.0 seconds.
C1-10
Acc./Dec. Time Switch Frequency
Sets the frequency level. The drive will switch the acceleration and deceleration time at this
level.
No.
Name
Setting Range
Default
C1-10
Acc./Dec. Time Switch Frequency
0.0 to <1><2>
0.0 Hz
<1> In control method of PM Closed-Loop Vector Control, the setting range is 0.0 to 100.0%,. The default setting is
0.0%.
<2> The upper limit is determined by the values set to d1-02 (Maximum Output Frequency), d1-13(Motor2
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit)
Note: This parameter will be disabled when 0.0 Hz (0.0%) is set to this parameter. <1> The setting range is