187
When the speed (signed) exceeds the P6-07 level, an oL (Mechanical Weakening Overtorque
Detection) alarm will be triggered and the drive will continue operation.
2 : Continue Operation if the Speed (Unsigned) is above P6-07
When the speed (unsigned) exceeds the P6-07 level, an oL (Mechanical Weakening
Overtorque Detection) alarm will be triggered and the drive will continue operation.
3 : Stop Operation if the Speed (Signed) is above P6-07
When the speed (signed) exceeds the P6-07 level, an oL (Mechanical Weakening Overtorque
Detection) fault will be triggered and the drive will stop operation.
4 : Stop Operation if the Speed (Unsigned) is above P6-07
When the speed (unsigned) exceeds the P6-07 level, an oL (Mechanical Weakening
Overtorque Detection) fault will be triggered and the drive will stop operation.
5 : Continue Operation if the Speed (Signed) is below P6-07
When the speed (signed) is below the P6-07 level, an UL (Mechanical Weakening Undertorque
Detection) alarm will be triggered and the drive will continue operation.
6 : Continue Operation if the Speed (Unsigned) is below P6-07
When the speed (unsigned) is below the P6-07 level, an UL (Mechanical Weakening
Undertorque Detection) alarm will be triggered and the drive will continue operation.
7 : Stop Operation if the Speed (Signed) is below P6-07
When the speed (signed) is below the P6-07 level, an UL (Mechanical Weakening Undertorque
Detection) fault will be triggered and the drive will stop operation.
8 : Stop Operation if the Speed (Unsigned) is below P6-07
When the speed (unsigned) is below the P6-07 level, an UL (Mechanical Weakening
Undertorque Detection) fault will be triggered and the drive will stop operation.
P6-07
Mechanical Weakening Detection Speed Level
Sets the speed level for Mechanical Weakening Detection as a percentage of d1-02 (Maximum
Output Frequency).
No.
Name
Setting Range
Default
P6-07
Mechanical Weakening Detection Speed Level
-110.0 to
110.0%
110.0%
The drive detects Mechanical Weakening by th settings of P6-00 to P6-02. When P6-06 is