Drive rated current
0
( 4mA )
10 V
( 20mA )
DC braking current level
Figure 6.65 DC Braking Current Using Analog Input
7 : Stall Prevention Level During Run
Adjusts the stall prevention level by the analog input signal. The stall prevention level is
determined by the analog input value or the P3-06 value whichever is smaller.
100%
Analog input level
0
( 4mA )
10 V
( 20mA )
Stall prevention level during Run
30%
3 V
( 8.8mA )
Figure 6.66 Stall Prevention Level Using Analog Input
8 : PID Feedback
Sets the PID feedback by the analog input value. To use this function, enable the PID control in
b5-00. Refer to b5-11 on page 79
9 : PID Target
Sets the PID target value by the analog input value. The frequency command entered by the
command source selected in b1-00 (Frequency Command Selection 1) is disabled. To use this
function, enable the PID control in b5-00. Refer to b5-11 on page 79 for details.
10: Differential PID Feedback