Same as b5-11= 0. Detection remains active when PID is disabled by a digital input (E1-□□=
46).
4 : Feedback Failure Alarm, ever if PID is Disabled
Same action as b5-11=1. Detection remains active when PID is disabled by a digital input
(E1-□□= 46).
5 : Feedback Failure Fault even if PID is Disabled
Same action as b5-11=2. Detection remains active when PID is disabled by a digital input
(E1-□□= 46).
6 :Multi-Function Output,
it continue to operate and light failure is not displayed
A feedback loss condition is detected when the PID feedback value falls below the value set in
parameter b5-12 (PID feedback loss detection level) for the time set in parameter b5-13 (PID
feedback loss detection time), E2- □□ = 40 terminal set is closed
A feedback loss condition is detected when the PID feedback value falls over the value set in
parameter b5-22 (PID feedback loss detection level) for the time set in parameter b5-23 (PID
feedback loss detection time), E2- □□ = 41 terminal set is closed
The invertor continues to operate. When the feedback value is not lost within the detection
range, the output will be reset.
7 :Multi-Function Output Only (Detection of non-operation is still valid)
Function 7 with the function 0, the difference lies in the function 0 must detect valid in
operation, function 7 in the non-operation effectively
b5- 12 PID Feedback Low Detection Level
Sets the PID feedback level used for detection. When the PID feedback falls below this level for
longer than the time set to b5-14, PID feedback loss will be detected.
No.
Name
Setting Range
Default
b5-12
PID Feedback Low Detection Level
0 to 100%
0%
b5- 13 PID Feedback Low Detection Time
Sets the PID feedback time used for detection. When the PID feedback falls below the level set
to b5-13 for longer than this time, PID feedback loss will be detected.
No.
Name
Setting Range
Default
b5-13
PID Feedback Low Detection Time
0.0 to 25.5 s
1.0 s