195
CAUTION!
An incorrect o2- 03 setting may cause the drive performance to suffer and drive damage.
No.
Name
Setting Range
Default
o2-03
Drive Capacity Selection
-
Determined by
drive capacity
Rating (kW)
(200V series)
0.25
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
o2-03 Setting
0
1
2
3
4
5
6
7
8
Rating (kW)
(200V series)
15
18.5
22
30
37
45
o2-03 Setting
9
10
11
12
13
14
Rating (kW)
(400V Series)
0.25
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
o2-03 Setting
32
33
34
35
36
37
38
39
40
Rating (kW)
(400V Series)
15
18.5
22
30
37
45
55
75
o2-03 Setting
41
42
43
44
45
46
47
48
o2-04
ENTER Key Function During Frequency Command Setting
Determines whether the ENTER key is required to be pressed after changing the frequency
command using the keypad in Local mode.
No.
Name
Setting Range
Default
o2-04
ENTER Key Function During Frequency Command
Setting
0,1
0
0 : ENTER Key Required
The ENTER key is required to be pressed to trigger the frequency command.
1 : ENTER Key Not Required
When entering a frequency command, the output frequency changes immediately by UP or
DOWN key without pressing ENTER. The frequency command will be saved 5 seconds after it is
changed by pressing the UP or DOWN key.
o2- 05
Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the digital operator is removed in LOCAL mode