52
4.4.2
Terminal A2 Voltage/Current Input Selection
Select voltage or current input at terminal A2
To select current as the input type, set DIP switch A2 to I and set parameter E3-06 to 0 (0
to 20 mA) or 1 (4 to 20 mA).
To select voltage as the input type, set DIP switch A2 to V and set parameter E3-06 to 2 (0
to 10 V) or 3 (0 to 5 V).
Figure 4.4.2 DIP Switch A2
Table 4.4.1 DIP Switch A2 Settings (Terminal A2)
Setting
Description
V
Voltage input (0 to 10 V or 0 to 5 V)
I
Current input (4 to 20 mA or 0 to 20 mA)
(
default)
Table 4.4.2 Parameter E3-06
No.
Parameter Name
Description
Setting Range Default
E3-06
Terminal A2 Signal Level
Selection
Selects the signal level for terminal A2.
0 : 0 ~ 20 mA
1 : 4 ~ 20 mA
2 : 0 ~ 10 V
3 : 0 ~ 5 V
0, 1, 2, 3
1
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...