122
■ V/F Pattern Settings d1- 02 to d1- 11
When d1-01
≤
E, the user can use d1-02 to d1-11 to monitor the V/F pattern settings. When
d1-01 = F, d1-02 to d1-11 can be set to create a new pattern as shown in Figure 6.42.
No.
Name
Setting Range
Default
d1-02
Maximum Output Frequency
25.0 to 400.0 Hz
<1>
d1-03
Maximum Voltage
0.0 to 255.0 V <3>
<1> <2>
d1-04
Base Frequency
0.0 to d1-02
<1>
d1-05
Base Voltage
0.0 to 255.0 V <3>
0.0 V <2> <3>
d1-06
Middle Output Frequency
0.0 to d1-02
<1>
d1-07
Middle Output Frequency
Voltage
0.0 to 255.0 V <3>
<1> <2>
d1-08
Minimum Output Frequency
0.0 to d1-02
<1>
d1-09
Minimum Output Frequency
Voltage
0.0 to 255.0 V <3>
<1> <2>
d1-10
Middle Output Frequency 2
0.0 to d1-02
0.0 Hz <4>
d1-11
Middle Output Frequency
Voltage 2
0.0 to 255.0 V <3>
0.0 V <2> <3>
<4>
<1> The default setting is determined by A1-02 (Control Method Selection). The settings in this table are the
default in Open-Loop V/F Control.
<2>This is the value for a 200 V AC drive. The value for a 400 V AC drive is doubled.
<3>This will be automatically changed in Auto-Tuning (rotational, stationary 1 or 2).
<4> d1-10 and d1-11 will be disabled when setting 0.0.
Output Voltage (V)
Frequency (Hz)
d1-08
d1-06
d1-04
d1-10
d1-02
d1-09
d1-07
d1-05
d1-11
d1-03
Figure 6.42 V/F Pattern