Enables or disables the protection to avoid an active Run command at the new source causing
a sudden movement on the motor when the command source is switched from the old source
to the new source.
No.
Name
Setting Range
Default
b1-05
Run Command Action after Switch
0, 1
0
0 : Ignore Active Run Command at the New Source
If a Run command at the new source is active, the drive will not start or the drive will stop
operation if it was running, when switching from the old source to the new source. The drive
can start only when the Run command is removed and given again.
1 : Accept Active Run Command at the New Source
WARNING!
If a run command at the new source is active, the drive will accept it and run the motor immediately
right after switching from the old source to the new source. Clear all personnel from the electrical connections and
the running machinery prior to switching command sources. Failure to comply could cause serious injury.
b1-05=1
b1-05=0
REMOTE
LOCAL
RE RUN
RE STOP
OUTPUT
b1-05=0,If a Run command at the new source is active, the drive will not start or the
drive will stop operation if it was running, when switching from the old source to the new
source. The drive can start only when the Run command is removed and given again.
b1-05=1,If a run command at the new source is active, the
drive will accept it and run the motor immediately right after
switching from the old source to the new source.
Figure 6.8.1 Run Command Action after Switch
b1-06 Run Command Selection during Programming
For safety reasons, the drive will ignore a Run command when the keypad is being used to edit
parameters in Programming Mode. If allowing a Run command during programming is
required in the application, set this parameter to 1.
No.
Name
Setting Range
Default
b1-06
Run Command Selection during Programming
0 to 2