163
0 : Pulse train input
1 : PWM signal input
Wiring:
RP
PC
PWM input
5V
17
19
The PWM signals are input to drive as signal level 5V via terminal RP.
ON Time
PWM Cycle
PWM Cycle
OFF Time
ON Time
OFF Time
E5-10
E5-10
Frequency command (Hz) =
On Time
PWM Cycle
✕
Maximum output frequency
When the input signal is high via terminal
Setting:
To use PWM signal as the frequency command source, set b1-00 or b1-07 to 4 (Pulse Train
Input), E5-00 to 0(Frequency Command) and E5-08 to 1 (PWM Signal Input). When E5-08
is set to 0 (Pulse Train Input), the drive will use pulse train input as the frequency
command source.
Keypad
Control circuit terminal
Terminal Up/Down
MODBUS通讯
PWM input
Pulse train input
1
0
0
1
2
3
4
Frequency
command source
E5-08
b1-00
b1-07
E5-00 = 0
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...