93
Displays the PID target in r/min. Number of Motor Poles must be set
3 : User Defined
Displays the PID target in the units defined by b5-24 and b5-25
b5- 20 PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output
frequency (d1-02). The lower limit is disabled when set to 0.00%
No.
Name
Setting Range
Default
b5-20
PID
Output Limit
-100.0 ~ 100.0%
0.0%
b5- 21 PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency
(d1-02). Parameter b5-21 acts as a bipolar limit.
No.
Name
Setting Range
Default
b5-21
PID Input Limit
0.0 ~ 1000.0%
1000.0%
b5- 22 PID Feedback High Detection Level
Sets the level for PID feedback high detection as a percentage of the maximum output
frequency.
PID feedback high will be detected when the feedback exceeds the level set in b5-22 for longer
than the time set in b5-23.
No.
Name
Setting Range
Default
b5-22
PID Feedback High Detection Level
0 to 100%
100%
b5- 23 PID Feedback High Detection Time
Sets the time for PID feedback high detection. PID feedback high will be detected when the
feedback exceeds the level set in b5-22 for longer than the time set in b5-23.
No.
Name
Setting Range
Default
b5-23
PID Feedback High Detection Time
0 to 25.5 s
1.0 s
b5- 24/b5- 25
PID Target Display Value/ PID Target Display Digits
When b5-19=3, b5-24 and b5-25 set a user-defined display for the PID feedback and target in
U4-00 and U4-03. When b5-19≠3, parameters b5-24 and b5-25 cannot be edited.
b5-24 Sets the display value when run at the maximum frequency.