n1- 00 Hunting Prevention Setting
Enables or disables the hunting prevention function.
Note: This function is only provided in V/F Control. When drive response is prioritized over suppressing motor
oscillation, disable Hunting Prevention. This function can be disabled without problems in applications with high
inertia loads or heavy loads.
No.
Name
Setting Range
Default
n1-00
Hunting Prevention Setting
0, 1
1
0 : Disabled
1 : Enabled
n1- 01 Hunting Prevention Gain
Sets the gain for Hunting Prevention.
No.
Name
Setting Range
Default
n1-01
Hunting Prevention Gain
0.00 to 2.50
1.00
Normally there is no need to change this setting. However, change the setting in the following
situations.
·
If the motor oscillates during light load, gradually increase this value by units of 0.1
·
If the motor stalls, gradually decrease this value by units of 0.1
6.9 Group o, Keypad Function Settings
o1 Display Setting
o1- 00 Frequency Command Setting/Display
o1-00 used to select the frequency command unit and monitor values. o1-00 = 3 and under
o1-02 and o1-03, the unit can be set to any。
No.
Name
Setting Range
Default
o1-00
Frequency Command
Setting/Display
0 ~ 3
0
0 :Use units of 0.01Hz
1 :Use units of 0.01%(100% as maximum output frequency)
2 :Use units of min-1 (automatically calculated by maximum output frequency and number
Содержание EVO 6800 Series