119
6.5 Group d, Motor Parameters
d parameters set the V/F characteristics and motor parameters.
d1 V/F Characteristics
d1- 00 Input Voltage Setting
Sets this parameter to match the input voltage of the drive as the base for detections such as
ov (Overvoltage) and Uv (Undervoltage).
Notice: To ensure the drive protection functions work properly, a
lways set the input voltage of the drive (not
motor) to this parameter.
Failure to comply could cause damage to the machinery or injury to personnel.
No.
Name
Setting Range
Default
d1-00<1>
Input Voltage Setting
155 to 255 V <1>
230 V <1>
<1> This is for a 200 V AC drive. The value is doubled for a 400 V AC drive.
□ Values Related to Drive Input Voltage
The following detection levels are determined by the drive input voltage.
Voltage
d1-00
setting
Approximate Values
ov
Detection
Level
P7-13
(DC Braking
Level) <1>
P2-03
(Detection
Level)
P2-08
(Voltage Target
During KEB)
P3-04
(Stall Prevention
Level during
Deceleration)
200 V
All settings
410 V
395 V
190 V
260 V
395
400 V
Setting
≥
400 V
820 V
790 V
380 V
500 V
790
Setting<
400 V
820 V
790 V
350 V
460 V
790
<1> The braking transistor operation level.
■ V/F Pattern Setting( d1-01)
The set V/F pattern determines the output voltage according to the frequency command.
There are 15 different preset V/F patterns (setting 0 to E: only the maximum voltage and base
voltage can be changed) and user-defined V/F patterns d1-02 to d1-11 (setting F).
d1- 01 V/F Pattern Selection
Selects 1 V/F pattern from the preset 15 ones or sets the user-defined V/F pattern.
No.
Name
Setting Range
Default
Содержание EVO 6800 Series
Страница 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Страница 33: ...33 34 2 36 0 2 8 93 0...
Страница 35: ...35 4 2 Main Circuit...
Страница 41: ...41 4 3 Control Circuit...
Страница 260: ...260 Above panel display value excluding the decimal point units please according to actual user unit conversion...